Southwire’s triplex Type RHH or RHW-2 or USE-2 AlumaFlex® is primarily used for secondary distribution and underground service at 600 volts or less, either directly burial or in ducts, where increased flexibility is needed. May also be used in conduit as specified by the NEC.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
378158 |
3
3
|
4 AWG
4 AWG
|
7
7
|
60
1.52
|
|
|
744
18.91
|
201
299
|
|
378117 |
3
3
|
2 AWG
2 AWG
|
7
7
|
60
1.52
|
|
|
870
22.11
|
239
355
|
|
378166 |
3
3
|
1/0 AWG
1/0 AWG
|
9
9
|
80
2.03
|
|
|
1105
28.09
|
395
588
|
|
378182 |
3
3
|
2/0 AWG
2/0 AWG
|
11
11
|
80
2.03
|
|
|
1198
30.45
|
501
746
|
|
334219 |
3
3
|
4/0 AWG
4/0 AWG
|
18
18
|
80
2.03
|
|
|
1421
36.10
|
819
1219
|
|
691964 |
4
4
|
4/0 AWG
4/0 AWG
|
18
18
|
80
2.03
|
|
|
1588
40.35
|
1005
1496
|
|
398982 |
3
3
|
250 KCMIL
250 KCMIL
|
22
22
|
95
2.41
|
|
|
1581
40.16
|
888
1321
|
|
399063 |
3
3
|
350 KCMIL
350 KCMIL
|
30
30
|
95
2.41
|
|
|
1794
45.59
|
1153
1716
|
|
Southwire’s triplex Type RHH or RHW-2 or USE-2 AlumaFlex® 600 volt cable meets or exceeds the following ASTM specifications:
Type RHH or RHW-2 or USE-2 AlumaFlex® conductors are compressed stranded TRIPLE E AA-8000 (8176-H24) series Aluminum Alloy insulated with cross-linked polyethylene. A triplex construction consists of two phase conductors and one neutral. The neutral conductor contains three yellow extruded stripes and sequential footage marks. Conductors are durably surface printed for identification.