Primarily used for 120 volt overhead service applications such as street lighting, outdoor lighting, and temporary service for construction. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 90°C for crosslinked polyethylene (XLP) insulated conductors.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
110718 |
3
3
|
6 AWG
6 AWG
|
7
7
|
45
1.14
|
|
|
578
14.70
|
271
403
|
|
110734 |
3
3
|
4 AWG
4 AWG
|
7
7
|
45
1.14
|
|
|
680
17.28
|
374
556
|
|
110775 |
3
3
|
2 AWG
2 AWG
|
7
7
|
45
1.14
|
|
|
805
20.46
|
585
871
|
|
110809 |
3
3
|
2/0 AWG
2/0 AWG
|
19
19
|
60
1.52
|
|
|
1136
28.86
|
1318
1961
|
|