Southwire’s 2.4KV ARMOR-X® Type MC-HL are armored cables for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial or concrete encasement and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 130°C for emergency overload, 250°C for short circuit conditions, and -50°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503. Suitable for VFD application.
Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Inner Layer Thickness (mils) (mm) | Ground Size | Diameter Over Armor (in) (cm) | Outer Layer Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | |
More Options |
2 AWG
2 AWG
|
7
7
|
0.282
0.72
|
0.495
1.26
|
90
2.29
|
3 x 10
3 x 10
|
1.430
3.63
|
70
1.78
|
1.570
3.99
|
1432
2131
|
1592
722.12
|
10.9
27.69
|
More Options |
1/0 AWG
1/0 AWG
|
19
19
|
0.361
0.92
|
0.580
1.47
|
90
2.29
|
3 x 8
3 x 8
|
1.540
3.91
|
60
1.52
|
1.660
4.22
|
1960
2917
|
2534
1149.40
|
11.6
29.46
|
More Options |
2/0 AWG
2/0 AWG
|
19
19
|
0.405
1.03
|
0.625
1.59
|
90
2.29
|
3 x 8
3 x 8
|
1.670
4.24
|
70
1.78
|
1.810
4.60
|
2338
3479
|
3194
1448.77
|
12.6
32.00
|
More Options |
250 KCMIL
250 KCMIL
|
37
37
|
0.558
1.42
|
0.770
1.96
|
90
2.29
|
3 x 6
3 x 6
|
2.040
5.18
|
60
1.52
|
2.166
5.50
|
3750
5581
|
6000
2721.55
|
15.1
38.35
|
More Options |
350 KCMIL
350 KCMIL
|
37
37
|
0.661
1.68
|
0.865
2.20
|
90
2.29
|
3 x 6
3 x 6
|
2.290
5.82
|
85
2.16
|
2.460
6.25
|
5276
7852
|
8400
3810.17
|
17.2
43.69
|
More Options |
500 KCMIL
500 KCMIL
|
37
37
|
0.789
2.00
|
0.990
2.51
|
90
2.29
|
3 x 4
3 x 4
|
2.670
6.78
|
75
1.91
|
2.820
7.16
|
6809
10133
|
12000
5443.10
|
19.7
50.04
|
More Options |
750 KCMIL
750 KCMIL
|
61
61
|
0.968
2.46
|
1.205
3.06
|
90
2.29
|
3 x 4
3 x 4
|
3.000
7.62
|
85
2.16
|
3.170
8.05
|
9734
14486
|
18000
8164.66
|
22.1
56.13
|
Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Allowable Ampacity In Duct 90C | Allowable Ampacity In Duct 105C | Allowable Ampacity In Air 90C | Allowable Ampacity In Air 105C | |
More Options |
2 AWG
2 AWG
|
0.162
0.24
|
0.204
0.30
|
0.035
0.05
|
0.186 + j0.02
0.186 + j0.02
|
0.196 + j0.029
0.196 + j0.029
|
135
135
|
145
145
|
140
140
|
154
154
|
More Options |
1/0 AWG
1/0 AWG
|
0.102
0.15
|
0.128
0.19
|
0.032
0.05
|
0.11 + j0.017
0.11 + j0.017
|
0.12 + j0.026
0.12 + j0.026
|
175
175
|
190
190
|
185
185
|
205
205
|
More Options |
2/0 AWG
2/0 AWG
|
0.081
0.12
|
0.102
0.15
|
0.032
0.05
|
0.084 + j0.016
0.084 + j0.016
|
0.094 + j0.025
0.094 + j0.025
|
200
200
|
220
220
|
215
215
|
240
240
|
More Options |
250 KCMIL
250 KCMIL
|
0.043
0.06
|
0.056
0.08
|
0.029
0.04
|
0.038 + j0.014
0.038 + j0.014
|
0.048 + j0.023
0.048 + j0.023
|
290
290
|
315
315
|
320
320
|
355
355
|
More Options |
350 KCMIL
350 KCMIL
|
0.031
0.05
|
0.041
0.06
|
0.028
0.04
|
0.023 + j0.013
0.023 + j0.013
|
0.033 + j0.022
0.033 + j0.022
|
355
355
|
380
380
|
395
395
|
440
440
|
More Options |
500 KCMIL
500 KCMIL
|
0.022
0.03
|
0.030
0.04
|
0.027
0.04
|
0.012 + j0.012
0.012 + j0.012
|
0.022 + j0.021
0.022 + j0.021
|
430
430
|
460
460
|
485
485
|
545
545
|
More Options |
750 KCMIL
750 KCMIL
|
0.014
0.02
|
0.023
0.03
|
0.027
0.04
|
0.005 + j0.011
0.005 + j0.011
|
0.015 + j0.02
0.015 + j0.02
|
530
530
|
570
570
|
615
615
|
685
685
|
* NEC ampacities are based on:
* For Duct: Table 310.60(C)(13) Detail 1.
* For Free Air: Table 310.60(C)(5).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
* Capacitive Reactance is between Phase-to-Shield.