Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Cond. Size (AWG/Kcmil) | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Ground (No. x AWG) | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Drain Wire | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Conduit Size (in) (cm) | |
589126 |
750
750
|
61
61
|
0.968
2.46
|
1.204
3.06
|
90
2.29
|
1.264
3.21
|
|
80
2.03
|
1.956
4.97
|
21x12
21x12
|
60
1.52
|
2.076
5.27
|
3988
5935
|
6000
2721.55
|
24.9
63.25
|
|
587711 |
500
500
|
37
37
|
0.789
2.00
|
0.992
2.52
|
90
2.29
|
1.052
2.67
|
|
80
2.03
|
1.732
4.40
|
17x12
17x12
|
60
1.52
|
1.852
4.70
|
2902
4319
|
4000
1814.37
|
22.2
56.39
|
|
Cond. Size (AWG/Kcmil) | DC Resistance @ 25C (ohms/1000') (ohms/km) | AC Resistance @ 75C (ohms/1000') (ohms/km) | Capacitive Reactance (Mohms x 1000ft) (Mohms x km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles (amps) | Direct Buried Ampacity @ 90C (amps) | Direct Buried Ampacity @ 105C (amps) | In Duct Ampacity @ 90C (amps) | In Duct Ampacity @ 105C (amps) | In Air Ampacity @ 90C (amps) | In Air Ampacity @ 105C (amps) | |
589126 |
750
750
|
0.014
0.02
|
0.023
0.03
|
0.009
0.01
|
0.039
0.06
|
0.356 + j0.262
0.356 + j0.262
|
0.024 + j0.039
0.024 + j0.039
|
26018
26018
|
551
551
|
|
|
|
706
706
|
|
587711 |
500
500
|
0.022
0.03
|
0.03
0.04
|
0.01
0.01
|
0.041
0.06
|
0.378 + j0.314
0.378 + j0.314
|
0.031 + j0.041
0.031 + j0.041
|
20275
20275
|
497
497
|
|
|
|
616
616
|
|