Southwire's 5kV / 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Cond. Size (AWG/Kcmil) | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Ground (No. x AWG) | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Drain Wire | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Conduit Size (in) (cm) | |
599001 |
4/0
4/0
|
19
19
|
0.512
1.30
|
0.766
1.95
|
115
2.92
|
0.826
2.10
|
|
110
2.79
|
2.397
6.09
|
|
75
1.91
|
2.547
6.47
|
4219
6279
|
5078
2303.34
|
17.8
45.21
|
|
640917 |
350
350
|
37
37
|
0.661
1.68
|
0.917
2.33
|
115
2.92
|
0.977
2.48
|
|
110
2.79
|
2.724
6.92
|
|
75
1.91
|
2.874
7.30
|
5967
8880
|
8400
3810.17
|
20.1
51.05
|
|
599006 |
500
500
|
37
37
|
0.789
2.00
|
1.042
2.65
|
115
2.92
|
1.102
2.80
|
|
110
2.79
|
2.994
7.60
|
|
75
1.91
|
3.144
7.99
|
7708
11471
|
12000
5443.10
|
22.0
55.88
|
|
671975 |
1
1
|
19
19
|
0.322
0.82
|
0.590
1.50
|
115
2.92
|
0.650
1.65
|
|
80
2.03
|
1.957
4.97
|
|
60
1.52
|
2.077
5.28
|
2356
3506
|
2008
910.81
|
14.5
36.83
|
|
Cond. Size (AWG/Kcmil) | DC Resistance @ 25C (ohms/1000') (ohms/km) | AC Resistance @ 75C (ohms/1000') (ohms/km) | Capacitive Reactance (Mohms x 1000ft) (Mohms x km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles (amps) | Direct Buried Ampacity @ 90C (amps) | Direct Buried Ampacity @ 105C (amps) | In Duct Ampacity @ 90C (amps) | In Duct Ampacity @ 105C (amps) | In Air Ampacity @ 90C (amps) | In Air Ampacity @ 105C (amps) | |
599001 |
4/0
4/0
|
0.051
0.08
|
0.065
0.10
|
0.024
0.04
|
0.034
0.05
|
0.439 + j0.399
0.439 + j0.399
|
0.065 + j0.034
0.065 + j0.034
|
2633
2633
|
372
372
|
|
|
|
342
342
|
|
640917 |
350
350
|
0.031
0.05
|
0.041
0.06
|
0.019
0.03
|
0.032
0.05
|
0.406 + j0.338
0.406 + j0.338
|
0.041 + j0.032
0.041 + j0.032
|
3120
3120
|
487
487
|
|
|
|
460
460
|
|
599006 |
500
500
|
0.022
0.03
|
0.03
0.04
|
0.016
0.02
|
0.03
0.04
|
0.385 + j0.297
0.385 + j0.297
|
0.030 + j0.030
0.030 + j0.030
|
3516
3516
|
573
573
|
|
|
|
556
556
|
|
671975 |
1
1
|
0.128
0.19
|
0.162
0.24
|
0.037
0.06
|
0.039
0.06
|
0.535 + j0.492
0.535 + j0.492
|
0.162 + j0.039
0.162 + j0.039
|
2044
2044
|
228
228
|
|
|
|
197
197
|
|