Southwire's Romex ® SIMpull ® NMD90 cables may be used for both exposed work in dry locations or concealed work in dry or damp locations. The maximum allowable conductor temperature is 90°C. The minimum recommended installation temperature is minus 25°C for three-conductor cables (with suitable handling procedures). Material should be properly stored above 0°C for 24 hours prior to installation. The maximum voltage rating for all intended applications is 300 volts. Consult the Canadian Electrical Code for further information related to applications.
Conductor | Ground Wire | Allowable Ampacities+ | |||||||
Size (AWG or kcmil) (mm2) | No. of Strands | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity at 60C | Allowable Ampacity at 75C | Allowable Ampacity at 90C | |
More Options |
6 AWG
6 AWG
|
7
7
|
8
8
|
7
7
|
753
19.15
|
219
326
|
40
40
|
50
50
|
55
55
|
More Options |
4 AWG
4 AWG
|
7
7
|
6
6
|
7
7
|
934
23.75
|
359
534
|
55
55
|
65
65
|
75
75
|
More Options |
2 AWG
2 AWG
|
6
6
|
6
6
|
7
7
|
1067
27.12
|
469
697
|
75
75
|
90
90
|
100
100
|
Southwire's Romex® SIMpull® NMD90 cables meet or exceed the requirements of:
The 3 conductor colours are black" red and white with PVC jacket.