600V SEOPRENE® SEOOW Cord Control with Black Jacket 105°C

600 Volt Cord. 105°C Premium Oil Resistance, Sunlight, Water Resistance and Flame Retardant

Download Category Specifications
Excel Table

Application

Southwire Type SEOOW Flexible Cords are permitted for Indoor and outdoor temporary power uses, portable industrial machinery and compressors, food processing and washdown facilities. Type SEOOW Cords are suitable for use in temperatures between -50°C to maximum 105°C.

Specifications

Select a set of products below for more information:
Conductor
Size (AWG or kcmil) (mm2) No. of Conductors No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity Nom. DC Resistance (Conductor) Conductor Colors
598758
18 AWG 18 AWG
6 6
16 16
484 12.29
117 173
5.5 5.5
6.4 6.4
BLACK/WHITE/RED/GREEN/ORANGE/BLUE BLACK/WHITE/RED/GREEN/ORANGE/BLUE
598728
18 AWG 18 AWG
7 7
16 16
488 12.40
125 186
4.5 4.5
6.4 6.4
BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK
598729
18 AWG 18 AWG
8 8
16 16
517 13.13
138 206
4.5 4.5
6.4 6.4
BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK/RED-BLACK BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK/RED-BLACK
598730
18 AWG 18 AWG
10 10
16 16
600 15.24
171 254
3.5 3.5
6.4 6.4
598731
18 AWG 18 AWG
12 12
16 16
613 15.58
190 283
3.5 3.5
6.4 6.4
598732
18 AWG 18 AWG
14 14
16 16
640 16.26
214 319
3.5 3.5
6.4 6.4
595487
18 AWG 18 AWG
16 16
16 16
697 17.70
256 381
3.5 3.5
6.4 6.4
550464
16 AWG 16 AWG
4 4
26 26
416 10.57
93 139
10 10
4.12 4.12
BLACK/WHITE/GREEN/RED BLACK/WHITE/GREEN/RED
550555
16 AWG 16 AWG
5 5
26 26
492 12.50
129 192
8 8
4.12 4.12
BLACK/WHITE/RED/GREEN/ORANGE BLACK/WHITE/RED/GREEN/ORANGE
562791
16 AWG 16 AWG
6 6
26 26
533 13.54
149 222
8 8
4.12 4.12
BLACK/WHITE/RED/GREEN/ORANGE/BLUE BLACK/WHITE/RED/GREEN/ORANGE/BLUE
595375
16 AWG 16 AWG
7 7
26 26
525 13.34
154 230
7 7
4.12 4.12
BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK
589888
16 AWG 16 AWG
8 8
26 26
560 14.22
174 258
7 7
4.12 4.12
BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK/RED-BLACK BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK/RED-BLACK
598736
16 AWG 16 AWG
14 14
26 26
725 18.42
287 427
5 5
4.12 4.12
598737
16 AWG 16 AWG
16 16
26 26
757 19.23
317 472
5 5
4.12 4.12
550562
14 AWG 14 AWG
2 2
41 41
497 12.62
113 169
18 18
2.64 2.64
BLACK/WHITE BLACK/WHITE
550398
14 AWG 14 AWG
3 3
41 41
522 13.26
137 204
18 18
2.64 2.64
BLACK/WHITE/GREEN BLACK/WHITE/GREEN
550399
14 AWG 14 AWG
4 4
41 41
592 15.04
180 268
15 15
2.64 2.64
BLACK/WHITE/RED/GREEN BLACK/WHITE/RED/GREEN
598739
14 AWG 14 AWG
6 6
41 41
690 17.53
248 369
12 12
2.64 2.64
BLACK/WHITE/RED/GREEN/ORANGE/BLUE BLACK/WHITE/RED/GREEN/ORANGE/BLUE
598740
14 AWG 14 AWG
7 7
41 41
690 17.53
262 390
10 10
2.64 2.64
BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK
598741
14 AWG 14 AWG
8 8
41 41
743 18.87
298 444
10 10
2.64 2.64
BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK/RED-BLACK BLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK/RED-BLACK
589921
14 AWG 14 AWG
10 10
41 41
835 21.21
357 531
7 7
2.64 2.64
550432
12 AWG 12 AWG
2 2
65 65
570 14.48
159 236
25 25
1.66 1.66
BLACK/WHITE BLACK/WHITE
550395
12 AWG 12 AWG
3 3
65 65
603 15.32
193 287
25 25
1.66 1.66
BLACK/WHITE/GREEN BLACK/WHITE/GREEN
598745
12 AWG 12 AWG
6 6
65 65
745 18.92
317 471
16 16
1.66 1.66
BLACK/WHITE/RED/GREEN/ORANGE/BLUE BLACK/WHITE/RED/GREEN/ORANGE/BLUE

Standards & References

  • UL 62 Flexible Cords and Cables
  • CSA C22.2 No. 49 Flexible Cords and Cables
  • Passes CSA FT2 Flame Test
  • RoHS-2 (European Directive 2011/65/EU)
  • NEC Article 400 Flexible Cords, Cables and Fixture Wire
  • NEC Article 501.140 Class I Division 2

Construction

  1. Conductor: Class K stranded bare copper per ASTM B-174
  2. Insulation: Heat, moisture and oil resistant TPE
  3. Filler: Non-wicking polypropylene fillers, with a tissue-paper separator wrapped around the assembly
  4. Jacket: Black TPE (other colors available upon request)