Southwire’s 15KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerially supported by a messenger and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend. For uses in Class I and II, Division 2 hazardous locations per NEC Article 501 and 502.Rated for 1000 lbs./FT maximum sidewall pressure.
Cond. Size (AWG/Kcmil) | 1/0 1/0 | |
Cond. Strands | 19 19 | |
Diameter Over Conductor (in) (cm) | 0.361 0.92 | inch cm |
Diameter Over Insulation (in) (cm) | 0.840 2.13 | inch cm |
Insulation Thickness (mils) (mm) | 220 5.59 | mils mm |
Diameter Over Shield (in) (cm) | 0.900 2.29 | inch cm |
Ground (No. x AWG) | 1x4 1x4 | |
Jacket Thickness (mils) (mm) | 110 2.79 | mils mm |
Approx. OD (in) (cm) | 2.215 5.63 | inch cm |
Approx. Weight (lbs/1000') (kgs/km) | 2758 4104 | lbs/1000' kgs/km |
Max Pull Tension (lbs) (kg) | 2534 1149.40 | lbs kg |
Min. Bend Radius (in) (cm) | 15.5 39.37 | inch cm |
^ 750kcmil Stock#: 653562 has a RED outer jacket