Southwire’s 35KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.
Cond. Size (AWG/Kcmil) | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Conduit Size (in) (cm) | |
More Options |
1/0
1/0
|
19
19
|
0.361
0.92
|
1.240
3.15
|
420
10.67
|
1.300
3.30
|
80
2.03
|
1.480
3.76
|
1249
1859
|
844
382.83
|
17.7
44.96
|
4.5
11.43
|
More Options |
2/0
2/0
|
19
19
|
0.405
1.03
|
1.284
3.26
|
420
10.67
|
1.344
3.41
|
80
2.03
|
1.524
3.87
|
1377
2049
|
1064
482.62
|
18.2
46.23
|
4.5
11.43
|
More Options |
4/0
4/0
|
19
19
|
0.512
1.30
|
1.390
3.53
|
420
10.67
|
1.450
3.68
|
80
2.03
|
1.630
4.14
|
1721
2561
|
1692
767.48
|
19.6
49.78
|
4.5
11.43
|
More Options |
250
250
|
37
37
|
0.558
1.42
|
1.428
3.63
|
420
10.67
|
1.488
3.78
|
110
2.79
|
1.728
4.39
|
1983
2951
|
2000
907.18
|
20.7
52.58
|
5.0
12.70
|
More Options |
350
350
|
37
37
|
0.661
1.68
|
1.527
3.88
|
420
10.67
|
1.587
4.03
|
110
2.79
|
1.827
4.64
|
2385
3549
|
2800
1270.06
|
21.9
55.63
|
5.5
13.97
|
More Options |
500
500
|
37
37
|
0.789
2.00
|
1.652
4.20
|
420
10.67
|
1.712
4.35
|
110
2.79
|
1.952
4.96
|
2976
4429
|
4000
1814.37
|
23.4
59.44
|
5.5
13.97
|
More Options |
750
750
|
61
61
|
0.968
2.46
|
1.864
4.73
|
420
10.67
|
1.924
4.89
|
110
2.79
|
2.164
5.50
|
3972
5911
|
6000
2721.55
|
25.9
65.79
|
6.0
15.24
|
More Options |
1250
1250
|
91
91
|
1.250
3.18
|
2.150
5.46
|
420
10.67
|
2.210
5.61
|
110
2.79
|
2.450
6.22
|
5816
8655
|
10000
4535.92
|
29.4
74.68
|
|
More Options |
250
250
|
37
37
|
0.558
1.42
|
1.428
3.63
|
420
10.67
|
1.488
3.78
|
110
2.79
|
1.728
4.39
|
1975
2939
|
2000
907.18
|
20.7
52.58
|
5.0
12.70
|
* Conduit size based on 3 phase 40% fill-factor without ground
^ Non SimPull Jacket. Non CSA listed.
Cond. Size (AWG/Kcmil) | DC Resistance @ 25C (ohms/1000') (ohms/km) | AC Resistance @ 75C (ohms/1000') (ohms/km) | Capacitive Reactance (Mohms x 1000ft) (Mohms x km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles (amps) | In Duct Ampacity @ 90C (amps) | In Duct Ampacity @ 105C (amps) | In Air Ampacity @ 90C (amps) | In Air Ampacity @ 105C (amps) | |
More Options |
1/0
1/0
|
0.102
0.15
|
0.128
0.19
|
0.064
0.10
|
0.054
0.08
|
0.465 + j0.274
0.465 + j0.274
|
0.129 + j0.054
0.129 + j0.054
|
4055
4055
|
200
200
|
215
215
|
260
260
|
290
290
|
More Options |
2/0
2/0
|
0.081
0.12
|
0.102
0.15
|
0.060
0.09
|
0.052
0.08
|
0.434 + j0.263
0.434 + j0.263
|
0.103 + j0.052
0.103 + j0.052
|
4192
4192
|
230
230
|
245
245
|
300
300
|
330
330
|
More Options |
4/0
4/0
|
0.051
0.08
|
0.065
0.10
|
0.050
0.07
|
0.048
0.07
|
0.387 + j0.237
0.387 + j0.237
|
0.066 + j0.049
0.066 + j0.049
|
4523
4523
|
295
295
|
315
315
|
395
395
|
445
445
|
More Options |
250
250
|
0.043
0.06
|
0.056
0.08
|
0.049
0.07
|
0.048
0.07
|
0.372 + j0.227
0.372 + j0.227
|
0.057 + j0.048
0.057 + j0.048
|
4690
4690
|
325
325
|
345
345
|
440
440
|
490
490
|
More Options |
350
350
|
0.031
0.05
|
0.041
0.06
|
0.044
0.07
|
0.045
0.07
|
0.347 + j0.207
0.347 + j0.207
|
0.042 + j0.045
0.042 + j0.045
|
5009
5009
|
390
390
|
415
415
|
545
545
|
605
605
|
More Options |
500
500
|
0.022
0.03
|
0.030
0.04
|
0.039
0.06
|
0.043
0.06
|
0.324 + j0.187
0.324 + j0.187
|
0.031 + j0.043
0.031 + j0.043
|
5406
5406
|
465
465
|
500
500
|
680
680
|
755
755
|
More Options |
750
750
|
0.014
0.02
|
0.023
0.03
|
0.034
0.05
|
0.040
0.06
|
0.3 + j0.161
0.3 + j0.161
|
0.024 + j0.04
0.024 + j0.04
|
5992
5992
|
565
565
|
610
610
|
870
870
|
970
970
|
More Options |
1250
1250
|
0.009
0.01
|
0.018
0.03
|
0.028
0.04
|
0.037
0.06
|
0.271 - j0.124
0.271 - j0.124
|
0.019 - j0.219
0.019 - j0.219
|
6878
6878
|
715
715
|
770
770
|
1185
1185
|
1320
1320
|
More Options |
250
250
|
0.043
0.06
|
0.056
0.08
|
0.049
0.07
|
0.048
0.07
|
0.372 + j0.227
0.372 + j0.227
|
0.057 + j0.048
0.057 + j0.048
|
4690
4690
|
325
325
|
345
345
|
440
440
|
490
490
|
* NEC ampacities are based on:
* For Duct: Table 310.60(C)(11) Detail 1.
* For Free Air: Table 310.60(C)(3).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center..
* Capacitive Reactance is between Phase-to-Shield.