SPEC25070 DURATRAY™ CU 600V XLPE Insulation. RHH/RHW-2/RW90 UL & CSA

Single Copper Conductors, XLPE Insulation, Sunlight Resistant, 600V, 90ºC MAX, -40ºC MIN, Gasoline & Oil Resistant

Download Category Specifications
PDF Excel Table

Application

Suitable for installation in Cable Trays, Underground Duct Banks - As per CE Code limitations (see Rule 12-2202) for grounding and bonding applications. Standard colour is black. Some sizes may be availabe in white, red, blue, yellow, brown, orange or grey. Green DuragroundTM also available.

Specifications

Select a set of products below for more information:
Cond. Size (AWG/Kcmil) Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Diameter Over Insulation (in) (cm) Ground (No. x AWG) Drain Wire Diameter Over Shield (in) (cm) Inner Jacket Thickness (mils) (mm) Diameter Over Armor (in) (cm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Aluminum Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
649139
1/0 1/0
1.0 1.0
19 19
0.361 0.92
80 2.03
0.528 1.34
326 485
395 588
649088
2/0 2/0
1.0 1.0
19 19
0.405 1.03
80 2.03
0.572 1.45
410 610
487 725
649148
3/0 3/0
1.0 1.0
19 19
0.456 1.16
80 2.03
0.622 1.58
518 771
602 896
649097
4/0 4/0
1.0 1.0
19 19
0.512 1.30
80 2.03
0.666 1.69
653 972
745 1109
649045
500 500
1.0 1.0
37 37
0.789 2.00
95 2.41
0.966 2.45
1543 2296
1705 2537
649048
750 750
1.0 1.0
61 61
0.968 2.46
110 2.79
1.200 3.05
2315 3445
2549 3793
649130
1000 1000
1.0 1.0
61 61
1.117 2.84
110 2.79
1.349 3.43
3087 4594
3354 4991
Cond. Size (AWG/Kcmil) Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance @ 25C (ohms/1000') (ohms/km) AC Resistance @ 75C (ohms/1000') (ohms/km) Capacitive Reactance (Mohms x 1000ft) (Mohms x km) Inductive Reactance (ohms/1000') (ohms/km) Shield Short Circuit Current 6 Cycles (amps) Raceway Ampacity @ 75C (amps) Raceway Ampacity @ 90C (amps)
649139
1/0 1/0
1.0 1.0
2.1 5.33
844 382.83
0.102 0.15
0.122 0.18
0.044 0.07
150 150
170 170
649088
2/0 2/0
1.0 1.0
2.2 5.59
1064 482.62
0.081 0.12
0.097 0.14
0.043 0.06
175 175
195 195
649148
3/0 3/0
1.0 1.0
2.4 6.10
1342 608.72
0.064 0.10
0.078 0.12
0.042 0.06
200 200
225 225
649097
4/0 4/0
1.0 1.0
2.6 6.60
1692 767.48
0.051 0.08
0.062 0.09
0.041 0.06
230 230
260 260
649045
500 500
1.0 1.0
3.8 9.65
4000 1814.37
0.022 0.03
0.029 0.04
0.039 0.06
380 380
430 430
649048
750 750
1.0 1.0
6.0 15.24
6000 2721.55
0.014 0.02
0.022 0.03
0.038 0.06
475 475
535 535
649130
1000 1000
1.0 1.0
6.7 17.02
8000 3628.74
0.011 0.02
0.018 0.03
0.037 0.06
545 545
615 615

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • CSA C22.2 No.230 Tray Cables - Rated TC-ER (1/0 AWG and Larger)
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA SUN RES - for Sunlight Resistant rating
  • CSA ST1 Smoke Test - marked FT4-ST1 (1/0 and Larger)
  • Oil Res I & Sun Res - AWG 8 & Larger

Construction

  1. Conductor: Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation: Cross Linked Polyethylene (XLPE)