SPEC45263 AL 600V PVC-Nylon Insulation PVC Jacket THHN/THWN-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Power Cable 600Volt Three Conductor Aluminum, Polyvinyl Chloride (PVC) with nylon layer insulation THHN Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground. Silicone Free

Download Category Specifications
PDF Excel Table

Application

Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone free

Specifications

Select a set of products below for more information:
Cond. Size (AWG/Kcmil) Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Diameter Over Insulation (in) (cm) Ground (No. x AWG) Drain Wire Diameter Over Shield (in) (cm) Inner Jacket Thickness (mils) (mm) Diameter Over Armor (in) (cm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Aluminum Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
675613
2 2
3.0 3.0
7 7
0.268 0.68
40 1.02
80 2.03
0.945 2.40
214 318
569 847
675618
1 1
3.0 3.0
8 8
0.298 0.76
50 1.27
80 2.03
1.052 2.67
263 391
661 984
675620
1/0 1/0
3.0 3.0
10 10
0.336 0.85
50 1.27
80 2.03
1.132 2.88
341 507
763 1135
675622
2/0 2/0
3.0 3.0
12 12
0.376 0.96
50 1.27
80 2.03
1.218 3.09
429 638
880 1310
675624
3/0 3/0
3.0 3.0
15 15
0.422 1.07
50 1.27
80 2.03
1.319 3.35
518 771
1001 1490
578218
4/0 4/0
3.0 3.0
3 3
0.474 1.20
50 1.27
80 2.03
1.432 3.64
667 993
1145 1704
583386
250 250
3.0 3.0
22 22
0.520 1.32
60 1.52
80 2.03
1.577 4.01
776 1155
1363 2028
599317
600 600
3.0 3.0
41 41
0.812 2.06
70 1.78
110 2.79
2.318 5.89
1914 2848
2925 4353
677400
750 750
3.0 3.0
58 58
0.908 2.31
70 1.78
110 2.79
2.522 6.41
2300 3423
3580 5328
Cond. Size (AWG/Kcmil) Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance @ 25C (ohms/1000') (ohms/km) AC Resistance @ 75C (ohms/1000') (ohms/km) Capacitive Reactance (Mohms x 1000ft) (Mohms x km) Inductive Reactance (ohms/1000') (ohms/km) Shield Short Circuit Current 6 Cycles (amps) Raceway Ampacity @ 75C (amps) Raceway Ampacity @ 90C (amps)
675613
2 2
3.0 3.0
3.8 9.65
1194 541.59
0.267 0.40
0.321 0.48
0.045 0.07
90 90
100 100
675618
1 1
3.0 3.0
5.3 13.46
1506 683.11
0.211 0.31
0.254 0.38
0.046 0.07
100 100
115 115
675620
1/0 1/0
3.0 3.0
5.7 14.48
1900 861.82
0.168 0.25
0.201 0.30
0.044 0.07
120 120
135 135
675622
2/0 2/0
3.0 3.0
6.1 15.49
2395 1086.35
0.133 0.20
0.16 0.24
0.043 0.06
135 135
150 150
675624
3/0 3/0
3.0 3.0
6.6 16.76
3020 1369.85
0.105 0.16
0.126 0.19
0.042 0.06
155 155
175 175
578218
4/0 4/0
3.0 3.0
7.2 18.29
3808 1727.28
0.084 0.13
0.1 0.15
0.041 0.06
180 180
205 205
583386
250 250
3.0 3.0
7.9 20.07
4500 2041.16
0.071 0.11
0.086 0.13
0.041 0.06
205 205
230 230
599317
600 600
3.0 3.0
13.9 35.31
10800 4898.79
0.029 0.04
0.037 0.06
0.039 0.06
340 340
385 385
677400
750 750
3.0 3.0
15.1 38.35
13500 6123.49
0.024 0.04
0.031 0.05
0.038 0.06
385 385
435 435

Standards & References

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 4

Construction

  1. Conductor: Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Insulation: Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN
  3. Grounding Conductor: Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  4. Filler: Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder: Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket: Polyvinyl Chloride (PVC) Jacket