ELECTRICAL AL 600V-UD

Aluminum Conductors. Cross-Linked Polyethylene (XLPE) Insulation.

Download Category Specifications
Excel Table

Application

Used for secondary distribution and underground service at 600 volts or less, either direct burial or in ducts.

Specifications

Select a set of products below for more information:
Conductor Ground Wire
No. of Conductors Size (AWG or kcmil) (mm2) No. of Strands Insulation Thickness (mils) (mm) Size (AWG) No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity
554189
3 3
6 AWG 6 AWG
7 7
60 1.52
643 16.35
132 196
554187
3 3
4 AWG 4 AWG
7 7
60 1.52
744 18.91
188 280
554186
4 4
4 AWG 4 AWG
7 7
60 1.52
831 21.13
251 374
554174
3 3
2 AWG 2 AWG
7 7
60 1.52
870 22.11
275 409
554173
4 4
2 AWG 2 AWG
7 7
60 1.52
972 24.71
337 502
554150
3 3
1/0 AWG 1/0 AWG
9 9
80 2.03
1105 28.09
443 660
554148
4 4
1/0 AWG 1/0 AWG
9 9
80 2.03
1235 31.39
535 796
554163
3 3
2/0 AWG 2/0 AWG
11 11
80 2.03
1198 30.45
480 715
554160
4 4
2/0 AWG 2/0 AWG
11 11
80 2.03
1339 34.03
659 981
554183
3 3
4/0 AWG 4/0 AWG
18 18
80 2.03
1421 36.10
792 1178
554182
4 4
4/0 AWG 4/0 AWG
18 18
80 2.03
1588 40.35
971 1444
554168
3 3
250 KCMIL 250 KCMIL
22 22
95 2.41
1568 39.83
852 1268
554179
3 3
350 KCMIL 350 KCMIL
30 30
95 2.41
1794 45.59
1117 1662
554188
3 3
500 KCMIL 500 KCMIL
34 34
95 2.41
2052 52.12
1592 2369

Standards & References

Southwire’s quadruplex or paralleled 600 volt secondary UD cable meets or exceeds the following ASTM specifications:

  • B230 Aluminum, 1350-H19 Wire for Electrical Purposes
  • B231 Aluminum 1350 Conductors, Concentric-Lay-Stranded

Construction

Conductors are stranded, compressed 1350-H16/H26 aluminum, insulated with cross-linked polyethylene. Neutrals are identified by triple yellow extruded stripe. Cables with “YES” neutrals have sequential footage markers. Conductors are durably surface printed for identification. Three phase conductors and one neutral conductor are cabled together to produce the quadruplex cable configuration.

  • 1350