Southwire's Single Conductor 1kV Teck 90 is a CSA approved armoured cable for Industrial and Commercial applications. FT4, -40C, HL, AG14 and 90°C rated for use in harsh Canadian environments. Rated for installation in cable trays, duct banks, direct burial, troughs, hazardous locations, continuous rigid cable supports, and concrete encaseable. CSA AG14 Acid Gas compliance. <ul> <li>-40°C - CSA Cold Bend and Impact Temperature</li> <li> -25°C - Min. Installation Temperature</li> <li> 90°C - Max. Continuous Operating Temperature</li> <li> 140°C for Emergency Overload Temperature</li> </ul>
Cond. Size (AWG/Kcmil) | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Ground (No. x AWG) | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Drain Wire | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Conduit Size (in) (cm) | |
597824 |
4/0
4/0
|
19
19
|
0.512
1.30
|
|
80
2.03
|
|
|
55
1.40
|
1.221
3.10
|
13x14
13x14
|
45
1.14
|
1.311
3.33
|
1271
1891
|
1692
767.48
|
9.1
23.11
|
|
586405 |
350
350
|
37
37
|
0.661
1.68
|
|
90
2.29
|
|
|
60
1.52
|
1.449
3.68
|
13x12
13x12
|
45
1.14
|
1.539
3.91
|
1935
2880
|
2800
1270.06
|
10.7
27.18
|
|
581915 |
500
500
|
37
37
|
0.789
2.00
|
|
90
2.29
|
|
|
60
1.52
|
1.574
4.00
|
17x12
17x12
|
55
1.40
|
1.684
4.28
|
2579
3838
|
4000
1814.37
|
11.7
29.72
|
|
576233 |
750
750
|
61
61
|
0.968
2.46
|
|
90
2.29
|
|
|
60
1.52
|
1.771
4.50
|
21x12
21x12
|
55
1.40
|
1.881
4.78
|
3572
5316
|
6000
2721.55
|
13.1
33.27
|
|
Cond. Size (AWG/Kcmil) | DC Resistance @ 25C (ohms/1000') (ohms/km) | AC Resistance @ 75C (ohms/1000') (ohms/km) | Capacitive Reactance (Mohms x 1000ft) (Mohms x km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles (amps) | Direct Buried Ampacity @ 90C (amps) | Direct Buried Ampacity @ 105C (amps) | In Duct Ampacity @ 90C (amps) | In Duct Ampacity @ 105C (amps) | In Air Ampacity @ 90C (amps) | In Air Ampacity @ 105C (amps) | |
597824 |
4/0
4/0
|
0.051
0.08
|
0.062
0.09
|
|
0.041
0.06
|
|
|
|
|
|
|
|
|
|
586405 |
350
350
|
0.031
0.05
|
0.039
0.06
|
|
0.04
0.06
|
|
|
|
|
|
|
|
|
|
581915 |
500
500
|
0.022
0.03
|
0.029
0.04
|
|
0.039
0.06
|
|
|
|
|
|
|
|
|
|
576233 |
750
750
|
0.014
0.02
|
0.022
0.03
|
|
0.038
0.06
|
|
|
|
|
|
|
|
|
|