Southwire’s 5KV TECK 90, 5000V, non-shielded, EPR insulated power cable is a CSA approved armoured cable for industrial and commercial medium voltage applications. FT4, -40°C, HL, AG14 and 90°C rated for use in harsh Canadian environments. Rated for installation in cable trays, duct banks, direct burial, troughs, hazardous locations, continuous rigid cable supports, and is concrete encaseable. <br> <ul> <li>-40°C - CSA Cold Bend and Impact Temperature</li> <li> -25°C - Min. Installation Temperature</li> <li> 90°C - Max. Continuous Operating Temperature</li> <li> 140°C for Emergency Overload Temperature</li> <li>250°C for Short Circuit Temperature</li> </ul>
Cond. Size (AWG/Kcmil) | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Ground (No. x AWG) | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Drain Wire | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Conduit Size (in) (cm) | |
568467 |
2
2
|
7
7
|
0.282
0.72
|
|
90
2.29
|
|
1x6
1x6
|
85
2.16
|
1.585
4.03
|
|
55
1.40
|
1.695
4.31
|
1541
2293
|
1592
722.12
|
11.8
29.97
|
|
568468 |
1
1
|
19
19
|
0.322
0.82
|
|
90
2.29
|
|
1x6
1x6
|
85
2.16
|
1.682
4.27
|
|
55
1.40
|
1.792
4.55
|
1788
2661
|
2008
910.81
|
12.5
31.75
|
|
568470 |
1/0
1/0
|
19
19
|
0.361
0.92
|
|
90
2.29
|
|
1x6
1x6
|
85
2.16
|
1.768
4.49
|
|
55
1.40
|
1.878
4.77
|
2055
3058
|
2534
1149.40
|
13.1
33.27
|
|
568471 |
2/0
2/0
|
19
19
|
0.405
1.03
|
|
90
2.29
|
|
1x6
1x6
|
85
2.16
|
1.874
4.76
|
|
55
1.40
|
1.984
5.04
|
2439
3630
|
3194
1448.77
|
13.8
35.05
|
|
568472 |
3/0
3/0
|
19
19
|
0.456
1.16
|
|
90
2.29
|
|
1x4
1x4
|
85
2.16
|
1.982
5.03
|
|
55
1.40
|
2.092
5.31
|
2894
4307
|
4027
1826.61
|
14.6
37.08
|
|
568473 |
4/0
4/0
|
19
19
|
0.512
1.30
|
|
90
2.29
|
|
1x4
1x4
|
115
2.92
|
2.135
5.42
|
|
55
1.40
|
2.245
5.70
|
3501
5210
|
5078
2303.34
|
15.7
39.88
|
|
568474 |
250
250
|
37
37
|
0.558
1.42
|
|
90
2.29
|
|
1x4
1x4
|
115
2.92
|
2.248
5.71
|
|
55
1.40
|
2.358
5.99
|
3959
5892
|
6000
2721.55
|
16.5
41.91
|
|
568475 |
350
350
|
37
37
|
0.661
1.68
|
|
90
2.29
|
|
1x3
1x3
|
115
2.92
|
2.505
6.36
|
|
65
1.65
|
2.637
6.70
|
5196
7732
|
8400
3810.17
|
18.4
46.74
|
|
568476 |
500
500
|
37
37
|
0.789
2.00
|
|
90
2.29
|
|
1x3
1x3
|
115
2.92
|
2.731
6.94
|
|
65
1.65
|
2.863
7.27
|
6806
10128
|
12000
5443.10
|
20.0
50.80
|
|
Cond. Size (AWG/Kcmil) | DC Resistance @ 25C (ohms/1000') (ohms/km) | AC Resistance @ 75C (ohms/1000') (ohms/km) | Capacitive Reactance (Mohms x 1000ft) (Mohms x km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles (amps) | Direct Buried Ampacity @ 90C (amps) | Direct Buried Ampacity @ 105C (amps) | In Duct Ampacity @ 90C (amps) | In Duct Ampacity @ 105C (amps) | In Air Ampacity @ 90C (amps) | In Air Ampacity @ 105C (amps) | |
568467 |
2
2
|
0.162
0.24
|
0.195
0.29
|
|
0.035
0.05
|
|
|
|
|
|
|
|
172
172
|
|
568468 |
1
1
|
0.128
0.19
|
0.154
0.23
|
|
0.034
0.05
|
|
|
|
|
|
|
|
197
197
|
|
568470 |
1/0
1/0
|
0.102
0.15
|
0.122
0.18
|
|
0.033
0.05
|
|
|
|
|
|
|
|
225
225
|
|
568471 |
2/0
2/0
|
0.081
0.12
|
0.097
0.14
|
|
0.032
0.05
|
|
|
|
|
|
|
|
260
260
|
|
568472 |
3/0
3/0
|
0.064
0.10
|
0.078
0.12
|
|
0.031
0.05
|
|
|
|
|
|
|
|
297
297
|
|
568473 |
4/0
4/0
|
0.051
0.08
|
0.062
0.09
|
|
0.03
0.04
|
|
|
|
|
|
|
|
342
342
|
|
568474 |
250
250
|
0.043
0.06
|
0.053
0.08
|
|
0.03
0.04
|
|
|
|
|
|
|
|
376
376
|
|
568475 |
350
350
|
0.031
0.05
|
0.039
0.06
|
|
0.028
0.04
|
|
|
|
|
|
|
|
460
460
|
|
568476 |
500
500
|
0.022
0.03
|
0.029
0.04
|
|
0.027
0.04
|
|
|
|
|
|
|
|
556
556
|
|