For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet, dry, or hazardous locations. Sunlight Resistant. Typical applications are for control. lighting and power circuits in: pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants. <br> <ul> <li>-40°C - CSA Cold Bend and Impact Temperature</li> <li> -40°C - Min. Installation Temperature</li> <li> 90°C - Max. Continuous Operating Temperature</li> </ul>
Cond. Size (AWG/Kcmil) | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Ground (No. x AWG) | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Drain Wire | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Conduit Size (in) (cm) | |
568448 |
14
14
|
7
7
|
0.070
0.18
|
|
45
1.14
|
|
1x14
1x14
|
65
1.65
|
0.690
1.75
|
|
45
1.14
|
0.780
1.98
|
279
415
|
131
59.42
|
5.4
13.72
|
|
596503 |
12
12
|
7
7
|
0.088
0.22
|
|
45
1.14
|
|
1x14
1x14
|
65
1.65
|
0.775
1.97
|
|
45
1.14
|
0.865
2.20
|
354
527
|
208
94.35
|
6.0
15.24
|
|
596503 |
12
12
|
7
7
|
0.088
0.22
|
|
45
1.14
|
|
1x14
1x14
|
65
1.65
|
0.775
1.97
|
|
45
1.14
|
0.865
2.20
|
354
527
|
208
94.35
|
6.0
15.24
|
|
582003 |
10
10
|
7
7
|
0.113
0.29
|
|
45
1.14
|
|
1x12
1x12
|
65
1.65
|
0.723
1.84
|
|
45
1.14
|
0.813
2.07
|
303
451
|
166
75.30
|
5.6
14.22
|
|
582003 |
10
10
|
7
7
|
0.113
0.29
|
|
45
1.14
|
|
1x12
1x12
|
65
1.65
|
0.723
1.84
|
|
45
1.14
|
0.813
2.07
|
303
451
|
166
75.30
|
5.6
14.22
|
|
568611 |
10
10
|
7
7
|
0.113
0.29
|
|
45
1.14
|
|
1x12
1x12
|
65
1.65
|
0.833
2.12
|
|
45
1.14
|
0.923
2.34
|
435
647
|
332
150.59
|
6.4
16.26
|
|
Cond. Size (AWG/Kcmil) | DC Resistance @ 25C (ohms/1000') (ohms/km) | AC Resistance @ 75C (ohms/1000') (ohms/km) | Capacitive Reactance (Mohms x 1000ft) (Mohms x km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles (amps) | Direct Buried Ampacity @ 90C (amps) | Direct Buried Ampacity @ 105C (amps) | In Duct Ampacity @ 90C (amps) | In Duct Ampacity @ 105C (amps) | In Air Ampacity @ 90C (amps) | In Air Ampacity @ 105C (amps) | |
568448 |
14
14
|
2.631
3.92
|
3.17
4.72
|
|
0.058
0.09
|
|
|
|
|
|
|
|
|
|
596503 |
12
12
|
1.662
2.47
|
2.002
2.98
|
|
0.054
0.08
|
|
|
|
|
|
|
|
|
|
596503 |
12
12
|
1.662
2.47
|
2.002
2.98
|
|
0.054
0.08
|
|
|
|
|
|
|
|
|
|
582003 |
10
10
|
1.04
1.55
|
1.253
1.86
|
|
0.05
0.07
|
|
|
|
|
|
|
|
|
|
582003 |
10
10
|
1.04
1.55
|
1.253
1.86
|
|
0.05
0.07
|
|
|
|
|
|
|
|
|
|
568611 |
10
10
|
1.04
1.55
|
1.253
1.86
|
|
0.05
0.07
|
|
|
|
|
|
|
|
|
|