SPEC25050 CSA TECK 90 1000V PVC CONTROL CABLE

1000V Multi Conductor, 14-10 AWG Copper, FT4 - Flame Retardancy Rating, XLPE Insulation, Aluminum Interlocked Armour, Sunlight Resistant, -40°C - 90°C, Rated HL, AG14

Download Category Specifications
PDF Excel Table

Application

For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet, dry, or hazardous locations. Sunlight Resistant. Typical applications are for control. lighting and power circuits in: pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants. <br> <ul> <li>-40°C - CSA Cold Bend and Impact Temperature</li> <li> -40°C - Min. Installation Temperature</li> <li> 90°C - Max. Continuous Operating Temperature</li> </ul>

Specifications

Select a set of products below for more information:
Cond. Size (AWG/Kcmil) Cond. Strands Diameter Over Conductor (in) (cm) Diameter Over Insulation (in) (cm) Insulation Thickness (mils) (mm) Diameter Over Shield (in) (cm) Ground (No. x AWG) Inner Jacket Thickness (mils) (mm) Diameter Over Armor (in) (cm) Drain Wire Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Approx. Weight (lbs/1000') (kgs/km) Max Pull Tension (lbs) (kg) Min. Bend Radius (in) (cm) Conduit Size (in) (cm)
568448
14 14
7 7
0.070 0.18
45 1.14
1x14 1x14
65 1.65
0.690 1.75
45 1.14
0.780 1.98
279 415
131 59.42
5.4 13.72
596503
12 12
7 7
0.088 0.22
45 1.14
1x14 1x14
65 1.65
0.775 1.97
45 1.14
0.865 2.20
354 527
208 94.35
6.0 15.24
596503
12 12
7 7
0.088 0.22
45 1.14
1x14 1x14
65 1.65
0.775 1.97
45 1.14
0.865 2.20
354 527
208 94.35
6.0 15.24
582003
10 10
7 7
0.113 0.29
45 1.14
1x12 1x12
65 1.65
0.723 1.84
45 1.14
0.813 2.07
303 451
166 75.30
5.6 14.22
582003
10 10
7 7
0.113 0.29
45 1.14
1x12 1x12
65 1.65
0.723 1.84
45 1.14
0.813 2.07
303 451
166 75.30
5.6 14.22
568611
10 10
7 7
0.113 0.29
45 1.14
1x12 1x12
65 1.65
0.833 2.12
45 1.14
0.923 2.34
435 647
332 150.59
6.4 16.26
Cond. Size (AWG/Kcmil) DC Resistance @ 25C (ohms/1000') (ohms/km) AC Resistance @ 75C (ohms/1000') (ohms/km) Capacitive Reactance (Mohms x 1000ft) (Mohms x km) Inductive Reactance (ohms/1000') (ohms/km) Zero Sequence Impedance (ohms/1000') (ohms/1000') Positive Sequence Impedance (ohms/1000') (ohms/1000') Shield Short Circuit Current 6 Cycles (amps) Direct Buried Ampacity @ 90C (amps) Direct Buried Ampacity @ 105C (amps) In Duct Ampacity @ 90C (amps) In Duct Ampacity @ 105C (amps) In Air Ampacity @ 90C (amps) In Air Ampacity @ 105C (amps)
568448
14 14
2.631 3.92
3.17 4.72
0.058 0.09
596503
12 12
1.662 2.47
2.002 2.98
0.054 0.08
596503
12 12
1.662 2.47
2.002 2.98
0.054 0.08
582003
10 10
1.04 1.55
1.253 1.86
0.05 0.07
582003
10 10
1.04 1.55
1.253 1.86
0.05 0.07
568611
10 10
1.04 1.55
1.253 1.86
0.05 0.07

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 131 Type TECK 90 Cable
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • CSA AG14 - Acid Gas Compliance
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test

Construction

  1. Conductor: Class B stranded copper, compressed or compact, in accordance with ASTM B3 and B8.
  2. Insulation: Cross-Linked Polyethylene (XLPE), Colour Code: 2/C black, white; 3/C red, black, blue; 4/C red, black, blue, white
  3. Grounding Conductors: Uninsulated Class B stranded grounding conductor
  4. Inner Jacket: Black Polyvinyl Chloride (PVC)
  5. Armor: Aluminum Interlocked Armour (AIA)
  6. Overall Jacket: Black PVC (optional colours available)