500-37 CU SIMpull RWU90 XLPE 1000V -40C WHITE

Southwire #: 59066399

SINGLE COPPER CONDUCTORS, XLPE INSULATION, 1000 VOLTS / -40ºC MIN, 90ºC MAX, SUNLIGHT RESISTANT.

Download Category Specifications
PDF Excel Table
Select Product Specifications
Construction
Outer Jacket / Armor Color
Packaging

Application

Southwire’s SIMpull ® RWU90 is designed for direct earth burial (with protection as required by the inspecting authority). For service entrance above or below ground.

  • The minimum recommended installation temperature is minus 40°C (with suitable handling procedures).
  • Maximum conductor temperature is 90°C.
  • SIMpull ® RWU90 conductors feature SIM Technology jackets which reduces the coefficient of friction, allowing cables to be installed without external lubricants, resulting in reduced labour and materials costs.

Specifications

Stock # 59066399 59066399
Size (AWG or kcmil) (mm2) 500 KCMIL 500 KCMIL
No. of Strands 37 37
Insulation Thickness (mils) (mm) 110 2.79 mils mm
Nom. OD (mils) (mm) 998 25.35 mils mm
Nominal Total Weight (lbs/1000') (kgs/km) 1681 2501 lbs/1000' kgs/km
Allowable Ampacity at 90C Direct Buried 548** 548**
Allowable Ampacity at 60C 320 320
Allowable Ampacity at 75C 380 380
Allowable Ampacity at 90C 430 430

All Ampacities derived from the 2012 Canadian Electrical Code
* See Rule 14-104 in the 2012 Canadian Electrical Code
** Derived from Table D12A in Appendix D of the CE Code as per Triplex cable formation as shown in Diagram B4-3 in Appendix B - for Non-Continuous loads. Based on an ambient temperature of 20°C
† Derived from Table 2 of the CE Code for Cable in Conduit. Not more than 3 copper conductors in a raceway. Based on an ambient temperature of 30°C
†† For 3-wire 120V/240V and 120V/208V service conductors in single dwellings, see notes under CEC Table 2. Allowable ampacity shall not be greater than 60 amps for No. 6 AWG nor greater than 200 amps for No. 2/0 AWG
‡ Contact sales representative for more information.

Standards & References

Southwire’s SIMpull ® RWU90 cables meet or exceed the following requirements:

  • CSA Standard C22.2 No. 38 File Listing: LL90458

Construction

  1. Single copper conductor with extra thickness on the moisture resistant, low temperature, cross linked polyethylene insulation.
  2. Rated at 1000 volts
  3. SIMpull ® conductors are SR rated for sunlight resistance.

Resources

There are no downloadable resources for this product.