SPEC: 10006

SIMpull XHHW-2®/RW90 Copper

Conductor size 8 AWG and larger. Power Cable 600 or 1000 Volt Single Conductor Copper, Cross Linked Polyethylene (XLPE) with SIMpull technology for easier pulling.

Download Category Specifications
PDF Excel Table

Application & Features

APPLICATION
Southwire Copper SIMpull XHHW-2®/RW90 conductors are primarily used in conduit, cable tray or other recognized raceways for services, feeders, and branch circuit wiring, as specified in the National Electrical Code. SIMpull XHHW-2®/RW90 copper conductors may be used in wet or dry locations at temperatures not to exceed 90°C. Voltage rating for XHHW-2 conductors is 600 volts or 1000 volts for all sizes. Suitable for use in Health Care Facilities per Section 517.160 of the National Electrical Code where a dielectric constant of less than 3.5 maybe specified. This cable is designed to be installed without the application of pulling lubricant. RW90 is for open wiring and use in raceways (except cable troughs and ventilated flexible cableways) in dry or wet locations as per Canadian Electrical Code. For open wiring exposed to the weather.

FEATURES
- SIS- 8 AWG
- Sunlight resistant
- -40°C Cold bend
- FT1
- Gasoline and Oil Resistant II
- CT Rated- 1/0 AWG and larger
- FT4- 350 kcmil and larger
- RoHS/REACH Compliant
- SPEC 10005 for circuit sizes 14 AWG, 12 AWG, and 10 AWG

Specifications

Select a set of products below for more information:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Inner Layer Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
8 AWG 8 AWG
1 1
7 7
0.141 0.36
45 1.14
0.238 0.60
50 74
64 95
More Options
6 AWG 6 AWG
1 1
7 7
0.177 0.45
45 1.14
0.274 0.70
81 121
97 144
More Options
4 AWG 4 AWG
1 1
7 7
0.225 0.57
45 1.14
0.321 0.82
128 190
148 220
More Options
3 AWG 3 AWG
1 1
7 7
0.252 0.64
45 1.14
0.348 0.88
162 241
184 274
More Options
2 AWG 2 AWG
1 1
7 7
0.282 0.72
45 1.14
0.379 0.96
204 304
228 339
More Options
1 AWG 1 AWG
1 1
19 19
0.322 0.82
55 1.40
0.435 1.10
258 384
291 433
More Options
1/0 AWG 1/0 AWG
1 1
19 19
0.361 0.92
55 1.40
0.480 1.22
326 485
363 540
More Options
2/0 AWG 2/0 AWG
1 1
19 19
0.405 1.03
55 1.40
0.524 1.33
410 610
452 673
More Options
3/0 AWG 3/0 AWG
1 1
19 19
0.456 1.16
55 1.40
0.574 1.46
518 771
564 839
More Options
4/0 AWG 4/0 AWG
1 1
19 19
0.512 1.30
55 1.40
0.630 1.60
655 975
707 1052
More Options
250 KCMIL 250 KCMIL
1 1
37 37
0.558 1.42
65 1.65
0.700 1.78
771 1147
838 1247
More Options
300 KCMIL 300 KCMIL
1 1
37 37
0.610 1.55
65 1.65
0.753 1.91
926 1378
998 1485
More Options
350 KCMIL 350 KCMIL
1 1
37 37
0.661 1.68
65 1.65
0.803 2.04
1080 1607
1158 1723
More Options
400 KCMIL 400 KCMIL
1 1
37 37
0.705 1.79
65 1.65
0.848 2.15
1235 1838
1317 1960
More Options
500 KCMIL 500 KCMIL
1 1
37 37
0.789 2.00
65 1.65
0.908 2.31
1543 2296
1632 2429
More Options
600 KCMIL 600 KCMIL
1 1
61 61
0.865 2.20
80 2.03
1.038 2.64
1852 2756
1973 2936
More Options
700 KCMIL 700 KCMIL
1 1
61 61
0.935 2.37
80 2.03
1.103 2.80
2161 3216
2284 3399
More Options
750 KCMIL 750 KCMIL
1 1
61 61
0.968 2.46
80 2.03
1.140 2.90
2315 3445
2449 3645
More Options
1000 KCMIL 1000 KCMIL
1 1
61 61
1.117 2.84
80 2.03
1.289 3.27
3087 4594
3240 4822
Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
8 AWG 8 AWG
1 1
1.0 2.54
132 59.87
0.653 0.97
0.786 1.17
0.052 0.08
50 50
55 55
More Options
6 AWG 6 AWG
1 1
1.1 2.79
209 94.80
0.411 0.61
0.495 0.74
0.051 0.08
65 65
75 75
More Options
4 AWG 4 AWG
1 1
1.3 3.30
333 151.05
0.258 0.38
0.310 0.46
0.048 0.07
85 85
95 95
More Options
3 AWG 3 AWG
1 1
1.4 3.56
420 190.51
0.205 0.31
0.246 0.37
0.047 0.07
100 100
115 115
More Options
2 AWG 2 AWG
1 1
1.5 3.81
530 240.40
0.162 0.24
0.195 0.29
0.045 0.07
115 115
130 130
More Options
1 AWG 1 AWG
1 1
1.7 4.32
669 303.45
0.128 0.19
0.154 0.23
0.046 0.07
130 130
145 145
More Options
1/0 AWG 1/0 AWG
1 1
1.9 4.83
844 382.83
0.102 0.15
0.122 0.18
0.044 0.07
150 150
170 170
More Options
2/0 AWG 2/0 AWG
1 1
2.1 5.33
1064 482.62
0.081 0.12
0.097 0.14
0.043 0.06
175 175
195 195
More Options
3/0 AWG 3/0 AWG
1 1
2.3 5.84
1342 608.72
0.064 0.10
0.078 0.12
0.042 0.06
200 200
225 225
More Options
4/0 AWG 4/0 AWG
1 1
2.5 6.35
1692 767.48
0.051 0.08
0.062 0.09
0.041 0.06
230 230
260 260
More Options
250 KCMIL 250 KCMIL
1 1
2.8 7.11
2000 907.18
0.043 0.06
0.053 0.08
0.041 0.06
255 255
290 290
More Options
300 KCMIL 300 KCMIL
1 1
3.0 7.62
2400 1088.62
0.036 0.05
0.045 0.07
0.041 0.06
285 285
320 320
More Options
350 KCMIL 350 KCMIL
1 1
3.2 8.13
2800 1270.06
0.031 0.05
0.039 0.06
0.040 0.06
310 310
350 350
More Options
400 KCMIL 400 KCMIL
1 1
3.4 8.64
3200 1451.49
0.027 0.04
0.035 0.05
0.040 0.06
335 335
380 380
More Options
500 KCMIL 500 KCMIL
1 1
3.6 9.14
4000 1814.37
0.022 0.03
0.029 0.04
0.039 0.06
380 380
430 430
More Options
600 KCMIL 600 KCMIL
1 1
5.2 13.21
4800 2177.24
0.018 0.03
0.025 0.04
0.039 0.06
420 420
475 475
More Options
700 KCMIL 700 KCMIL
1 1
5.5 13.97
5600 2540.12
0.015 0.02
0.022 0.03
0.038 0.06
460 460
520 520
More Options
750 KCMIL 750 KCMIL
1 1
5.7 14.48
6000 2721.55
0.014 0.02
0.022 0.03
0.038 0.06
475 475
535 535
More Options
1000 KCMIL 1000 KCMIL
1 1
6.4 16.26
8000 3628.74
0.011 0.02
0.018 0.03
0.037 0.06
545 545
615 615

* Ampacities based upon 2023 NEC Table 310.16 Raceway or Cable, Not more than 3 copper conductors on an ambient temperature of 30°C.
* Ampacities derived from the 2021 Canadian Electrical Code. - Table 2 - for Raceway or Cable. Not more than 3 copper conductors on an ambient temperature of 30°C.
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

Size (Strand) Black Red Blue White Brown Orange Yellow Gray Purple Green
14 (7) 14 (7)
955351 955351
12 (7) 12 (7)
955344 955344
10 (7) 10 (7)
955336 955336
8 (7) 8 (7)
112953 952713 553059 952721 553060 553061 553062 553063
952739
6 (7) 6 (7)
112961 952705 959916 678607 683383 683391 553067 553068
553230
4 (7) 4 (7)
112979 952697 553846 678599 553847 553848 553849 553850
558627
3 (7) 3 (7)
267278 652971 652972 652973 677646 677647 652975 677648
890469
2 (7) 2 (7)
112987 218115 553087 218107 553088 553089 553090
674066 474122
1 (19) 1 (19)
112995 550761 550762 550808 553854 553855 553856 553857 674065 550766
1/0 (19) 1/0 (19)
113001 553860 553861 553858 553863 553864 553865 553866 674064 553862
2/0 (19) 2/0 (19)
113019 553871 553872 553870 553873 553874 553876 553877 553878 552070
3/0 (19) 3/0 (19)
113027 553881 553882 553880 553885 553886 553887 553888 674063 553884
4/0 (19) 4/0 (19)
113035 553078 553079 553077 553080 553082 553083 553084 674062 552071
250 (37) 250 (37)
113043 553893 553894 553892 553896 553897 553898 553899 674061 553895
300 (37) 300 (37)
113050 643848 643849 643850 561129 561130 561131 584039 139410 580121
350 (37) 350 (37)
113068 553903 553904 553902 553906 553907 553908 553910 674060 553905
400 (37) 400 (37)
113076 561701 561702 561132 561111 561112 561113 561703
558666
500 (37) 500 (37)
113084 550369 550261 553071 550260 550262 550259 553074 553075 553072
600 (61) 600 (61)
113092 553914 553915 553913 553918 553919 553920 553921 589214 553916
700 (61) 700 (61)
586272
662840 662842 662843 662844
750 (61) 750 (61)
113100 553927 553928 553926 553930 553931 553932 553934
553929
1000 (61) 1000 (61)
113134 138623 138622 138624 678463 678465 678464
668449

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B787 19 Wire Combination Unilay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202/FT4 Flame Test (70,000 BTU/hr) 350kcmil and Larger
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • Federal Specification A-A-59544
  • NMX-J-451-ANCE Thermoset insulated wires and cables
  • NOM-063-SCFI Electrical Products – Conductors – Safety Requirements

Construction

  1. Conductor: Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation: Cross Linked Polyethylene (XLPE) with SIMpull Technology. Silicone-Free, Abrasion, High-Heat, Moisture Resistant

Resources