1/0-259 CU 15KV JUMPER CABLE RED

Southwire #: 56942399

Single Conductor Flexible Conductor with an EPR Insulation Non-Shielded Jumper Cable

Download Category Specifications
PDF Excel Table
Select Product Specifications
Construction
Outer Jacket / Armor Color
Packaging

Application

Southwire’s medium voltage non-shielded jumper and switchgear cable is a flexible power cable that is intended for use in substations installed on insulators and inside switchgear isolated from ground and where a non-shielded flexible cable is desired. These cables are capable of operating continuously at a conductor temperature not in excess of 90°C. See Table 2 for installation guidelines. This cable is rated up to 40KV and is not UL listed.

Specifications

Stock # 56942399 56942399
Cond. Size (AWG/Kcmil) 1/0 1/0
Conductor Number 1.0 1.0
Cond. Strands 259 259
Diameter Over Conductor (in) (cm) 0.379 0.96 inch cm
Insulation Thickness (mils) (mm) 210 5.33 mils mm
Approx. OD (in) (cm) 0.840 2.13 inch cm
Approx. Weight (lbs/1000') (kgs/km) 548 816 lbs/1000' kgs/km

Standards & References

  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors

Construction

  1. Conductor: Flexible rope lay stranded annealed bare or tinned copper
  2. Conductor Shield: Nylon semi-conducting tape, helically applied
  3. Insulation: Heat, moisture, and ozone resistant Ethylene Propylene Rubber(EPR)

Resources

There are no downloadable resources for this product.