Southwire’s Instrumentation Cables Type TC-ER per UL 1277 are suitable for installations as outlined in NEC Article 336 for process control and instrumentation, control circuits for operation and interconnection of protective and signaling devices and for general use in manufacturing, industrial and commercial distribution systems. Cables are constructed with 7-strand tinned copper conductors insulated with Ethylene Propylene Rubber EPR. The paired conductors are colored black, white, and alpha-numeric printed. The overall assembly is covered with an aluminum polyester foil with 100% coverage and a tinned drain wire. The cable is suited for use in cable trays, raceways, conduit, aerial (when supported with a messenger) and direct burial. The cable is rated for -30°C to 90°C wet or dry and rated for Class I Div II hazardous locations, sun and oil resistant. The jacket is black Chlorinated Polyethylene CPE with a rip cord for easy removal. 1 Pair is not TC-ER Rated.
Cond. Size | Conductor Number | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Min. Bend Radius (in) (cm) | DC Resistance at 25C (ohms/1000') (ohms/km) | |
More Options |
18 AWG
18 AWG
|
1
1
|
0.045
0.11
|
30
0.76
|
45
1.14
|
0.309
0.78
|
46
68
|
1.8
4.57
|
6.669
9.92
|
More Options |
18 AWG
18 AWG
|
5
5
|
0.045
0.11
|
30
0.76
|
60
1.52
|
0.714
1.81
|
178
265
|
4.2
10.67
|
6.669
9.92
|
More Options |
18 AWG
18 AWG
|
12
12
|
0.045
0.11
|
30
0.76
|
80
2.03
|
0.941
2.39
|
377
561
|
5.6
14.22
|
6.669
9.92
|
More Options |
16 AWG
16 AWG
|
1
1
|
0.056
0.14
|
30
0.76
|
45
1.14
|
0.333
0.85
|
57
85
|
1.9
4.83
|
4.181
6.22
|
More Options |
16 AWG
16 AWG
|
4
4
|
0.056
0.14
|
30
0.76
|
60
1.52
|
0.589
1.50
|
177
263
|
3.5
8.89
|
4.181
6.22
|
† 1 Pair is not TC-ER Rated.
Size AWG |
Capacitance pF/ft |
Inductance µH/ft |
18
18
|
40.66
40.66
|
0.0957
0.0957
|
16
16
|
48.51
48.51
|
0.0895
0.0895
|