Southwire’s 2.4KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation, 130°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.
Cond. Size (AWG/Kcmil) | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Ground (No. x AWG) | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Drain Wire | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Conduit Size (in) (cm) | |
607457 |
2
2
|
7
7
|
0.282
0.72
|
0.570
1.45
|
125
3.18
|
|
|
|
|
|
25
0.64
|
0.746
1.89
|
413
615
|
530
240.40
|
5.9
14.99
|
2.5
6.35
|
607465 |
1
1
|
19
19
|
0.322
0.82
|
0.610
1.55
|
125
3.18
|
|
|
|
|
|
85
2.16
|
0.786
2.00
|
484
720
|
669
303.45
|
6.2
15.75
|
2.5
6.35
|
607226 |
1/0
1/0
|
19
19
|
0.361
0.92
|
0.650
1.65
|
125
3.18
|
|
|
|
|
|
85
2.16
|
0.826
2.10
|
568
845
|
844
382.83
|
6.6
16.76
|
2.5
6.35
|
607234 |
2/0
2/0
|
19
19
|
0.405
1.03
|
0.695
1.77
|
125
3.18
|
|
|
|
|
|
85
2.16
|
0.871
2.21
|
671
999
|
1064
482.62
|
6.9
17.53
|
2.5
6.35
|
607242 |
3/0
3/0
|
19
19
|
0.456
1.16
|
0.745
1.89
|
125
3.18
|
|
|
|
|
|
105
2.67
|
0.955
2.43
|
830
1235
|
1342
608.72
|
7.6
19.30
|
3.0
7.62
|
607259 |
4/0
4/0
|
19
19
|
0.512
1.30
|
0.785
1.99
|
125
3.18
|
|
|
|
|
|
105
2.67
|
0.995
2.53
|
978
1455
|
1692
767.48
|
7.9
20.07
|
3.0
7.62
|
607267 |
250
250
|
37
37
|
0.558
1.42
|
0.870
2.21
|
140
3.56
|
|
|
|
|
|
120
3.05
|
1.112
2.82
|
1179
1755
|
2000
907.18
|
8.8
22.35
|
3.5
8.89
|
607283 |
350
350
|
37
37
|
0.661
1.68
|
0.965
2.45
|
140
3.56
|
|
|
|
|
|
120
3.05
|
1.207
3.07
|
1531
2278
|
2800
1270.06
|
9.6
24.38
|
3.5
8.89
|
607309 |
500
500
|
37
37
|
0.789
2.00
|
1.090
2.77
|
140
3.56
|
|
|
|
|
|
115
2.92
|
1.322
3.36
|
2039
3034
|
4000
1814.37
|
10.5
26.67
|
4.0
10.16
|
607119 |
750
750
|
61
61
|
0.968
2.46
|
1.335
3.39
|
155
3.94
|
|
|
|
|
|
135
3.43
|
1.611
4.09
|
3038
4521
|
6000
2721.55
|
12.8
32.51
|
4.5
11.43
|
607325 |
1000
1000
|
61
61
|
1.117
2.84
|
1.485
3.77
|
155
3.94
|
|
|
|
|
|
135
3.43
|
1.761
4.47
|
3893
5793
|
8000
3628.74
|
14.0
35.56
|
5.0
12.70
|
Cond. Size (AWG/Kcmil) | DC Resistance @ 25C (ohms/1000') (ohms/km) | AC Resistance @ 75C (ohms/1000') (ohms/km) | Capacitive Reactance (Mohms x 1000ft) (Mohms x km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles (amps) | Direct Buried Ampacity @ 90C (amps) | Direct Buried Ampacity @ 105C (amps) | In Duct Ampacity @ 90C (amps) | In Duct Ampacity @ 105C (amps) | In Air Ampacity @ 90C (amps) | In Air Ampacity @ 105C (amps) | |
607457 |
2
2
|
0.162
0.24
|
0.204
0.30
|
|
0.0434
0.06
|
|
|
|
|
|
145
145
|
155
155
|
190
190
|
215
215
|
607465 |
1
1
|
0.128
0.19
|
0.162
0.24
|
|
0.0417
0.06
|
|
|
|
|
|
170
170
|
180
180
|
225
225
|
250
250
|
607226 |
1/0
1/0
|
0.102
0.15
|
0.128
0.19
|
|
0.0401
0.06
|
|
|
|
|
|
195
195
|
210
210
|
260
260
|
290
290
|
607234 |
2/0
2/0
|
0.081
0.12
|
0.102
0.15
|
|
0.0387
0.06
|
|
|
|
|
|
220
220
|
235
235
|
300
300
|
330
330
|
607242 |
3/0
3/0
|
0.064
0.10
|
0.081
0.12
|
|
0.0381
0.06
|
|
|
|
|
|
250
250
|
270
270
|
345
345
|
385
385
|
607259 |
4/0
4/0
|
0.051
0.08
|
0.065
0.10
|
|
0.0368
0.05
|
|
|
|
|
|
290
290
|
310
310
|
400
400
|
445
445
|
607267 |
250
250
|
0.043
0.06
|
0.056
0.08
|
|
0.0373
0.06
|
|
|
|
|
|
320
320
|
345
345
|
445
445
|
495
495
|
607283 |
350
350
|
0.031
0.05
|
0.041
0.06
|
|
0.0355
0.05
|
|
|
|
|
|
385
385
|
415
415
|
550
550
|
615
615
|
607309 |
500
500
|
0.022
0.03
|
0.03
0.04
|
|
0.0337
0.05
|
|
|
|
|
|
470
470
|
505
505
|
695
695
|
775
775
|
607119 |
750
750
|
0.014
0.02
|
0.023
0.03
|
|
0.0329
0.05
|
|
|
|
|
|
585
585
|
630
630
|
900
900
|
1000
1000
|
607325 |
1000
1000
|
0.011
0.02
|
0.019
0.03
|
|
0.0317
0.05
|
|
|
|
|
|
670
670
|
720
720
|
1075
1075
|
1200
1200
|