MCAP® Type MC All Purpose

14 AWG through 8 AWG Copper THHN Insulated Conductors. Full-Sized Aluminum Equipment Grounding/ Bonding Conductor. UL Listed. 600 Volt. Rated VW1. Lightweight Aluminum Interlocked Armor is Part of Equipment Bonding/Grounding Path.

Download Category Specifications
PDF Excel Table

Application

Southwire MCAP ® Type MC Cable - All Purpose is suitable for use as follows:

  • Wherever standard AC or MC Cable is permitted.
  • Branch circuit wiring in commercial, industrial, institutional, and multi-residential buildings.
  • Fished or embedded in plaster.
  • Concealed or exposed installations.
  • Environmental air-handling spaces per NEC 300.22 (C).
  • Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
  • Installation in cable tray and approved raceways.
  • Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2).
  • Use UL Listed Type MCI-A connectors

Specifications

Select a set of products below for more information:
Conductor Ground Wire
No. of Conductors Size (AWG or kcmil) (mm2) No. of Strands Insulation Thickness (mils) (mm) Size (AWG) Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km)
More Options
2 2
14 AWG 14 AWG
1 1
15 0.38
12 12
451 11.47
70 105
More Options
3 3
14 AWG 14 AWG
1 1
15 0.38
12 12
468 11.90
88 130
More Options
4 4
14 AWG 14 AWG
1 1
15 0.38
12 12
498 12.66
106 157
More Options
2 2
12 AWG 12 AWG
1 1
15 0.38
10 10
487 12.37
92 137
More Options
3 3
12 AWG 12 AWG
1 1
15 0.38
10 10
506 12.88
118 175
More Options
4 4
12 AWG 12 AWG
1 1
15 0.38
10 10
544 13.82
145 216
More Options
6 6
12 AWG 12 AWG
1 1
15 0.38
610 15.49
199 297
More Options
2 2
10 AWG 10 AWG
1 1
20 0.51
8 8
555 14.12
131 195
More Options
3 3
10 AWG 10 AWG
1 1
20 0.51
8 8
580 14.74
170 253
More Options
4 4
10 AWG 10 AWG
1 1
20 0.51
8 8
619 15.74
210 313
More Options
6 6
10 AWG 10 AWG
1 1
20 0.51
709 18.03
293 436
More Options
2 2
8 AWG 8 AWG
19 19
30 0.76
8 8
688 17.48
199 296
More Options
2 2
12 AWG 12 AWG
1 1
15 0.38
10 10
487 12.37
92 137

Standards & References

Southwire MCAP® Type MC Cable meets or exceeds the following:

  • UL 83 • UL 1569 • UL 1063
  • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
  • NFPA 70 (National Electrical Code), Article 330 • Federal Specification A-A59544 (formerly J-C-30B)
  • FT4/IEEE 1202 (70,000 Btu/hr) Vertical Cable Tray Flame Test
  • Listed for use in UL 1, 2, and 3 Hour Through-Penetration Firestop Systems
  • REACH/RoHS-2 (Chemical Limit) Compliant

Construction

Southwire MCAP ® Type MC Cable is constructed with solid soft-drawn copper Type THHN circuit conductors rated 90ºC dry and a full-sized bare 8000 Series aluminum grounding/bonding conductor. This cable is available in sizes 14-8 AWG. The insulated conductors are cabled together and wrapped with a binder tape bearing the print legend. The bare aluminum grounding/bonding conductor is located outside the binding tape and has the same lay as the insulated conductors. Aluminum interlocking armor is snugly applied over the assembly. The aluminum armor and bare aluminum conductor are in intimate contact and together form the equipment ground path. To ensure proper installation, refer to the installation instructions provided with every reel and coil.

  1. An armor assembly that is an equipment grounding conductor per NEC 250.118(10)(b).
  2. Installation instructions included with every reel and coil.
  3. Simplified product application and installation over other armored products.
  4. Faster conductor make-up, wiring device installation and trim-out when grounding bonding conductor is terminated per installation instructions.
  5. Reduces installation costs up to 50% over pipe and wire.
  6. UL Classified 1, 2, and 3 hour Through Penetration Firestop Systems: W-J-3037, W-L-3110, W-L-3113, W-L-3117, W-L-3120, W-L-3121, W-L-3160, C-AJ-3115, C-AJ-3140, C-AJ-3142, C-AJ-3145, C-AJ-3173, C-AJ-3202, C-AJ-4065, C-AJ-4066, F-C-3038.
  7. Cable reverse wound on reel for ease of pulling and installation. When pulling from coils, pull from inside to ensure ease of installation.
  8. Anti-short bushings are not required for use with MC cable per the NEC and UL