SPEC: 45258

CU 600/1000V XLPE Insulation PVC Jacket XHHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Power Cable 600 or 1000 Volt Four Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. Silicone Free. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Download Category Specifications
PDF Excel Table

Application

Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free

Specifications

Select a set of products below for more information:
Cond. Size (AWG/Kcmil) Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Ground (No. x AWG) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
8 8
4 4
7 7
0.141 0.36
45 1.14
1x10 1x10
60 1.52
0.755 1.92
238 354
403 600
More Options
6 6
4 4
7 7
0.177 0.45
45 1.14
1x8 1x8
60 1.52
0.902 2.29
378 563
613 912
More Options
4 4
4 4
7 7
0.225 0.57
45 1.14
1x8 1x8
80 2.03
0.918 2.33
572 851
804 1196
More Options
2 2
4 4
7 7
0.282 0.72
45 1.14
1x6 1x6
80 2.03
1.046 2.66
909 1353
1185 1763
More Options
1 1
4 4
19 19
0.322 0.82
55 1.40
1x6 1x6
80 2.03
1.202 3.05
1125 1674
1496 2226
More Options
1/0 1/0
4 4
19 19
0.361 0.92
55 1.40
1x6 1x6
80 2.03
1.299 3.30
1399 2082
1754 2610
More Options
2/0 2/0
4 4
19 19
0.405 1.03
55 1.40
1x6 1x6
80 2.03
1.420 3.61
1742 2592
2144 3191
More Options
3/0 3/0
4 4
19 19
0.456 1.16
55 1.40
1x4 1x4
80 2.03
1.521 3.86
2223 3308
2693 4008
More Options
4/0 4/0
4 4
19 19
0.512 1.30
55 1.40
1x4 1x4
110 2.79
1.721 4.37
2769 4121
3425 5097
More Options
250 250
4 4
37 37
0.558 1.42
65 1.65
1x4 1x4
110 2.79
1.842 4.68
3248 4834
4003 5957
More Options
350 350
4 4
37 37
0.661 1.68
65 1.65
1x3 1x3
110 2.79
2.095 5.32
4530 6741
5351 7963
More Options
500 500
4 4
37 37
0.789 2.00
65 1.65
1x2 1x2
110 2.79
2.382 6.05
6443 9588
7427 11053
More Options
600 600
4 4
61 61
0.865 2.20
80 2.03
1x4/0 1x4/0
140 3.56
2.867 7.28
8144 12120
9633 14335
More Options
750 750
4 4
61 61
0.968 2.46
80 2.03
1x1 1x1
140 3.56
2.962 7.52
9616 14310
11320 16846
Cond. Size (AWG/Kcmil) Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance @ 25C (ohms/1000') (ohms/km) AC Resistance @ 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Raceway Ampacity @ 75C (amps) Raceway Ampacity @ 90C (amps)
More Options
8 8
4 4
3.0 7.62
422 191.42
0.653 0.97
0.786 1.17
0.052 0.08
40 40
44 44
More Options
6 6
4 4
3.6 9.14
671 304.36
0.411 0.61
0.495 0.74
0.051 0.08
52 52
60 60
More Options
4 4
4 4
3.7 9.40
1068 484.44
0.258 0.38
0.310 0.46
0.048 0.07
68 68
76 76
More Options
2 2
4 4
5.2 13.21
1698 770.20
0.162 0.24
0.195 0.29
0.045 0.07
92 92
104 104
More Options
1 1
4 4
6.0 15.24
2142 971.59
0.128 0.19
0.154 0.23
0.046 0.07
104 104
116 116
More Options
1/0 1/0
4 4
6.5 16.51
2703 1226.06
0.102 0.15
0.122 0.18
0.044 0.07
120 120
136 136
More Options
2/0 2/0
4 4
7.1 18.03
3407 1545.39
0.081 0.12
0.097 0.14
0.043 0.06
140 140
156 156
More Options
3/0 3/0
4 4
7.6 19.30
4295 1948.18
0.064 0.10
0.078 0.12
0.042 0.06
160 160
180 180
More Options
4/0 4/0
4 4
8.6 21.84
5416 2456.65
0.051 0.08
0.062 0.09
0.041 0.06
184 184
208 208
More Options
250 250
4 4
9.2 23.37
6400 2902.99
0.043 0.06
0.053 0.08
0.041 0.06
204 204
232 232
More Options
350 350
4 4
12.6 32.00
8960 4064.18
0.031 0.05
0.039 0.06
0.040 0.06
248 248
280 280
More Options
500 500
4 4
14.3 36.32
12800 5805.98
0.022 0.03
0.029 0.04
0.039 0.06
304 304
344 344
More Options
600 600
4 4
17.2 43.69
15360 6967.17
0.018 0.03
0.025 0.04
0.039 0.06
336 336
380 380
More Options
750 750
4 4
17.8 45.21
19200 8708.97
0.014 0.02
0.022 0.03
0.038 0.06
380 380
428 428

* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test

Construction

  1. Conductor: Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation: Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor: Class B compressed stranded bare copper per ASTM B3 and ASTM B8 (cable size 8 & 6 has insulated green ground)
  4. Filler: Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder: Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket: Polyvinyl Chloride (PVC) Jacket