Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. CT Rated 1/0 and Larger - Sunlight Resistant - Silicone Free. Rated for 1000 lbs./FT maximum sidewall pressure.
Cond. Size (AWG/Kcmil) | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Approx. OD (in) (cm) | Copper Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
More Options |
1/0
1/0
|
0
0
|
19
19
|
0.361
0.92
|
80
2.03
|
0.530
1.35
|
326
485
|
396
589
|
More Options |
2/0
2/0
|
1
1
|
19
19
|
0.405
1.03
|
80
2.03
|
0.572
1.45
|
410
610
|
488
726
|
More Options |
3/0
3/0
|
1
1
|
19
19
|
0.456
1.16
|
80
2.03
|
0.624
1.58
|
518
771
|
603
897
|
More Options |
4/0
4/0
|
1
1
|
19
19
|
0.512
1.30
|
80
2.03
|
0.680
1.73
|
653
972
|
748
1113
|
More Options |
250
250
|
1
1
|
37
37
|
0.558
1.42
|
95
2.41
|
0.742
1.88
|
771
1147
|
892
1327
|
More Options |
350
350
|
1
1
|
37
37
|
0.661
1.68
|
95
2.41
|
0.861
2.19
|
1080
1607
|
1223
1820
|
More Options |
500
500
|
1
1
|
37
37
|
0.789
2.00
|
95
2.41
|
0.966
2.45
|
1543
2296
|
1707
2540
|
More Options |
750
750
|
1
1
|
61
61
|
0.968
2.46
|
110
2.79
|
1.171
2.97
|
2315
3445
|
2544
3786
|
Cond. Size (AWG/Kcmil) | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance @ 25C (ohms/1000') (ohms/km) | AC Resistance @ 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Raceway Ampacity @ 75C (amps) | Raceway Ampacity @ 90C (amps) | |
More Options |
1/0
1/0
|
0
0
|
2.1
5.33
|
844
382.83
|
0.102
0.15
|
0.122
0.18
|
0.044
0.07
|
150
150
|
170
170
|
More Options |
2/0
2/0
|
1
1
|
2.2
5.59
|
1064
482.62
|
0.081
0.12
|
0.097
0.14
|
0.043
0.06
|
175
175
|
195
195
|
More Options |
3/0
3/0
|
1
1
|
2.4
6.10
|
1342
608.72
|
0.064
0.10
|
0.078
0.12
|
0.042
0.06
|
200
200
|
225
225
|
More Options |
4/0
4/0
|
1
1
|
2.7
6.86
|
1692
767.48
|
0.051
0.08
|
0.062
0.09
|
0.041
0.06
|
230
230
|
260
260
|
More Options |
250
250
|
1
1
|
2.9
7.37
|
2000
907.18
|
0.043
0.06
|
0.053
0.08
|
0.041
0.06
|
255
255
|
290
290
|
More Options |
350
350
|
1
1
|
3.4
8.64
|
2800
1270.06
|
0.031
0.05
|
0.039
0.06
|
0.040
0.06
|
310
310
|
350
350
|
More Options |
500
500
|
1
1
|
3.8
9.65
|
4000
1814.37
|
0.022
0.03
|
0.029
0.04
|
0.039
0.06
|
380
380
|
430
430
|
More Options |
750
750
|
1
1
|
5.9
14.99
|
6000
2721.55
|
0.014
0.02
|
0.022
0.03
|
0.038
0.06
|
475
475
|
535
535
|
* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
* Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.