CU FRXLPE CPE-TP SHIELDED CONTROL CABLE

Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Shielded Chlorinated Polyethylene Chloride (CPE) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free

Download Category Specifications
PDF Excel Table

Application

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated construction can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Only UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications

Select a set of products below for more information:
Conductor Ground Wire
No. of Conductors Size (AWG or kcmil) (mm2) No. of Strands Insulation Thickness (mils) (mm) Size (AWG) No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity
603689
2 2
12 AWG 12 AWG
7 7
30 0.76
456 11.59
141 209
603691
4 4
12 AWG 12 AWG
7 7
30 0.76
591 15.02
230 343
603692
5 5
12 AWG 12 AWG
7 7
30 0.76
621 15.78
261 388
619307
7 7
12 AWG 12 AWG
7 7
30 0.76
604 15.34
292 434
603697
9 9
12 AWG 12 AWG
7 7
30 0.76
772 19.61
410 610
619311
12 12
12 AWG 12 AWG
7 7
30 0.76
774 19.68
462 688
622946
2 2
10 AWG 10 AWG
7 7
30 0.76
580 14.74
204 303
618435
4 4
10 AWG 10 AWG
7 7
30 0.76
573 14.56
260 387
662216
5 5
10 AWG 10 AWG
7 7
30 0.76
685 17.42
344 512
619310
7 7
10 AWG 10 AWG
7 7
30 0.76
681 17.31
405 603
603709
9 9
10 AWG 10 AWG
7 7
30 0.76
876 22.27
564 840
662217
12 12
10 AWG 10 AWG
7 7
30 0.76
975 24.78
723 1076
603699
12 12
12 AWG 12 AWG
7 7
30 0.76
897 22.79
546 812

Standards & References

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • VW-1 (Vertical-Wire) Flame Test

Construction

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. LCT Shielding:5 mils tape shield
  6. Rip Chord:Rip chord for ease of jacket removal
  7. Overall Jacket:Chlorinated Polyethylene Chloride (CPE)
  8. Color codes available upon request