SPEC25031 CSA TECK 90 CU 3/C 5000V NON-SHIELDED TRXLPE POWER CABLE

5000V, Non-Shielded, TRXLPE Insulated, FT4, -40°C, HL (Hazardous Locations), AG14 & 90°C

Download Category Specifications
PDF Excel Table

Application

Southwire’s Teck 90, 5000V, non-shielded, TRXLPE insulated (treeing resistant) power cable is a CSA approved armoured cable for industrial and commercial medium voltage applications. FT4, -40°C, HL, AG14 and 90°C rated for use in harsh Canadian environments. Rated for installation in cable trays, duct banks, direct burial, troughs, hazardous locations, continuous rigid cable supports, and is concrete encaseable. <br> <ul> <li>-40°C - CSA Cold Bend and Impact Temperature</li> <li> -25°C - Min. Installation Temperature</li> <li> 90°C - Max. Continuous Operating Temperature</li> <li> 140°C for Emergency Overload Temperature</li> <li>250°C for Short Circuit Temperature</li> </ul>

Specifications

Select a set of products below for more information:
Cond. Size (AWG/Kcmil) Cond. Strands Diameter Over Conductor (in) (cm) Diameter Over Insulation (in) (cm) Insulation Thickness (mils) (mm) Diameter Over Shield (in) (cm) Ground (No. x AWG) Inner Jacket Thickness (mils) (mm) Diameter Over Armor (in) (cm) Drain Wire Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Approx. Weight (lbs/1000') (kgs/km) Max Pull Tension (lbs) (kg) Min. Bend Radius (in) (cm) Conduit Size (in) (cm)
573334
2 2
7 7
0.282 0.72
90 2.29
1x6 1x6
85 2.16
1.585 4.03
55 1.40
1.695 4.31
1523 2266
1592 722.12
11.8 29.97
586789
1/0 1/0
19 19
0.361 0.92
90 2.29
1x6 1x6
85 2.16
1.764 4.48
55 1.40
1.874 4.76
2011 2993
2534 1149.40
13.1 33.27
577418
4/0 4/0
19 19
0.512 1.30
90 2.29
1x4 1x4
115 2.92
2.135 5.42
55 1.40
2.245 5.70
3448 5131
5078 2303.34
15.7 39.88
568924
250 250
37 37
0.558 1.42
90 2.29
1x4 1x4
115 2.92
2.282 5.80
65 1.65
2.414 6.13
3981 5924
6000 2721.55
16.8 42.67
580964
350 350
37 37
0.661 1.68
90 2.29
1x3 1x3
115 2.92
2.461 6.25
65 1.65
2.593 6.59
5095 7582
8400 3810.17
18.1 45.97
568927
500 500
37 37
0.789 2.00
90 2.29
1x3 1x3
115 2.92
2.731 6.94
65 1.65
2.863 7.27
6713 9990
12000 5443.10
20.0 50.80
582272
750 750
61 61
0.968 2.46
90 2.29
1x2 1x2
145 3.68
3.252 8.26
80 2.03
3.420 8.69
9801 14585
18000 8164.66
23.9 60.71
577417
2/0 2/0
19 19
0.405 1.03
90 2.29
1x6 1x6
85 2.16
1.869 4.75
55 1.40
1.979 5.03
2391 3558
3194 1448.77
13.8 35.05
Cond. Size (AWG/Kcmil) DC Resistance @ 25C (ohms/1000') (ohms/km) AC Resistance @ 75C (ohms/1000') (ohms/km) Capacitive Reactance (Mohms x 1000ft) (Mohms x km) Inductive Reactance (ohms/1000') (ohms/km) Zero Sequence Impedance (ohms/1000') (ohms/1000') Positive Sequence Impedance (ohms/1000') (ohms/1000') Shield Short Circuit Current 6 Cycles (amps) Direct Buried Ampacity @ 90C (amps) Direct Buried Ampacity @ 105C (amps) In Duct Ampacity @ 90C (amps) In Duct Ampacity @ 105C (amps) In Air Ampacity @ 90C (amps) In Air Ampacity @ 105C (amps)
573334
2 2
0.162 0.24
0.195 0.29
0.035 0.05
172 172
586789
1/0 1/0
0.102 0.15
0.122 0.18
0.033 0.05
225 225
577418
4/0 4/0
0.051 0.08
0.062 0.09
0.03 0.04
342 342
568924
250 250
0.043 0.06
0.053 0.08
0.03 0.04
376 376
580964
350 350
0.031 0.05
0.039 0.06
0.028 0.04
460 460
568927
500 500
0.022 0.03
0.029 0.04
0.027 0.04
556 556
582272
750 750
0.014 0.02
0.022 0.03
0.027 0.04
678 678
577417
2/0 2/0
0.081 0.12
0.097 0.14
0.032 0.05
260 260

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 131 Type TECK 90 Cable
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • CSA AG14 - Acid Gas Compliance
  • ICEA S-96-659 (NEMA WC 71) 2001-5000 V Nonshielded Cables
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)

Construction

  1. Conductor: Class B stranded copper, compressed or compact, in accordance with ASTM B3 and B8.
  2. Conductor Shield: Extruded semi-conducting thermosetting polymeric layer
  3. Insulation: TRXLPE (cross-linked polyethylene), Thickness: 0.090” (2.3 mm) - nominal, 90°C
  4. Grounding Conductor: Class B compressed or compact stranded bare copper, in accordance with ASTM B3 and B8
  5. Binder: Polypropylene tape
  6. Inner Jacket: Black PVC, Thickness: No. 2 AWG to No. 3/0 AWG = 0.080” (2.0 mm); No. 4/0 AWG to 500 kcmil = 0.110” (2.8 mm); 750 kcmil to 1000 kcmil = 0.140” (3.6 mm)
  7. Armor: Aluminum Interlocked Armour (AIA)
  8. Overall Jacket: Orange PVC (optional colours available), Thickness: No. 2 AWG to 250 kcmil = 0.060” (1.5 mm); 350 kcmil to 750 kcmil = 0.075” (1.9 mm); 1000 kcmil = 0.090” (2.3 mm)