Southwire’s 5KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -40°C for cold bend and cold impact and marked with "LTGG" when CSA listed or dual UL/CSA listed. For uses in Class I and II, Division 2 hazardous locations per NEC Article 501 and 502.Rated for 1000 lbs./FT maximum sidewall pressure.
Cond. Size (AWG/Kcmil) | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Ground (No. x AWG) | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Drain Wire | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Conduit Size (in) (cm) | |
599065 |
2
2
|
7
7
|
0.268
0.68
|
0.536
1.36
|
115
2.92
|
0.596
1.51
|
1x4
1x4
|
|
|
|
80
2.03
|
1.499
3.81
|
1123
1671
|
1194
541.59
|
10.4
26.42
|
|
599070 |
3/0
3/0
|
18
18
|
0.422
1.07
|
0.691
1.76
|
115
2.92
|
0.751
1.91
|
1x4
1x4
|
|
|
|
110
2.79
|
1.894
4.81
|
1783
2653
|
3020
1369.85
|
13.2
33.53
|
|
581876 |
4/0
4/0
|
19
19
|
0.474
1.20
|
0.743
1.89
|
115
2.92
|
0.803
2.04
|
1x4
1x4
|
|
|
|
110
2.79
|
2.006
5.10
|
2069
3079
|
3808
1727.28
|
14.0
35.56
|
|
580932 |
350
350
|
35
35
|
0.615
1.56
|
0.892
2.27
|
115
2.92
|
0.952
2.42
|
1x3
1x3
|
|
|
|
110
2.79
|
2.334
5.93
|
2808
4179
|
6300
2857.63
|
16.3
41.40
|
|
Cond. Size (AWG/Kcmil) | DC Resistance @ 25C (ohms/1000') (ohms/km) | AC Resistance @ 75C (ohms/1000') (ohms/km) | Capacitive Reactance (Mohms x 1000ft) (Mohms x km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles (amps) | Direct Buried Ampacity @ 90C (amps) | Direct Buried Ampacity @ 105C (amps) | In Duct Ampacity @ 90C (amps) | In Duct Ampacity @ 105C (amps) | In Air Ampacity @ 90C (amps) | In Air Ampacity @ 105C (amps) | |
599065 |
2
2
|
0.267
0.40
|
0.336
0.50
|
0.036
0.05
|
0.041
0.06
|
0.705 + j0.524
0.705 + j0.524
|
0.336 + j0.041
0.336 + j0.041
|
1877
1877
|
|
|
105
105
|
110
110
|
110
110
|
120
120
|
599070 |
3/0
3/0
|
0.105
0.16
|
0.133
0.20
|
0.025
0.04
|
0.035
0.05
|
0.509 + j0.438
0.509 + j0.438
|
0.133 + j0.034
0.133 + j0.034
|
2354
2354
|
|
|
180
180
|
195
195
|
195
195
|
215
215
|
581876 |
4/0
4/0
|
0.084
0.13
|
0.105
0.16
|
0.023
0.03
|
0.034
0.05
|
0.48 + j0.414
0.48 + j0.414
|
0.105 + j0.033
0.105 + j0.033
|
2515
2515
|
|
|
205
205
|
220
220
|
225
225
|
250
250
|
580932 |
350
350
|
0.05
0.07
|
0.065
0.10
|
0.019
0.03
|
0.032
0.05
|
0.434 + j0.353
0.434 + j0.353
|
0.065 + j0.031
0.065 + j0.031
|
2977
2977
|
|
|
280
280
|
310
310
|
310
310
|
345
345
|