Southwire’s 8KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. Rated for 1000 lbs./FT maximum sidewall pressure. CT rated 1/0 and larger.
Cond. Size (AWG/Kcmil) | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Ground (No. x AWG) | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Drain Wire | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Conduit Size (in) (cm) | |
584285 |
4/0
4/0
|
19
19
|
0.512
1.30
|
0.816
2.07
|
140
3.56
|
0.876
2.23
|
|
|
|
|
80
2.03
|
1.056
2.68
|
1086
1616
|
1692
767.48
|
12.6
32.00
|
3.0
7.62
|
555204 |
500
500
|
37
37
|
0.789
2.00
|
1.092
2.77
|
140
3.56
|
1.152
2.93
|
|
|
|
|
80
2.03
|
1.332
3.38
|
2127
3165
|
4000
1814.37
|
15.9
40.39
|
4.0
10.16
|
568211 |
750
750
|
61
61
|
0.968
2.46
|
1.304
3.31
|
140
3.56
|
1.364
3.46
|
|
|
|
|
80
2.03
|
1.544
3.92
|
3019
4493
|
6000
2721.55
|
18.5
46.99
|
4.5
11.43
|
Cond. Size (AWG/Kcmil) | DC Resistance @ 25C (ohms/1000') (ohms/km) | AC Resistance @ 75C (ohms/1000') (ohms/km) | Capacitive Reactance (Mohms x 1000ft) (Mohms x km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles (amps) | Direct Buried Ampacity @ 90C (amps) | Direct Buried Ampacity @ 105C (amps) | In Duct Ampacity @ 90C (amps) | In Duct Ampacity @ 105C (amps) | In Air Ampacity @ 90C (amps) | In Air Ampacity @ 105C (amps) | |
584285 |
4/0
4/0
|
0.051
0.08
|
0.065
0.10
|
0.025
0.04
|
0.039
0.06
|
0.433 + j0.38
0.433 + j0.38
|
0.065 + j0.039
0.065 + j0.039
|
2788
2788
|
|
|
295
295
|
315
315
|
400
400
|
445
445
|
555204 |
500
500
|
0.022
0.03
|
0.03
0.04
|
0.018
0.03
|
0.034
0.05
|
0.378 + j0.284
0.378 + j0.284
|
0.031 + j0.034
0.031 + j0.034
|
3671
3671
|
|
|
465
465
|
500
500
|
685
685
|
765
765
|
568211 |
750
750
|
0.014
0.02
|
0.023
0.03
|
0.015
0.02
|
0.032
0.05
|
0.353 + j0.238
0.353 + j0.238
|
0.024 + j0.032
0.024 + j0.032
|
4257
4257
|
|
|
565
565
|
610
610
|
885
885
|
990
990
|