Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Only UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
618791 |
3
3
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
386
9.83
|
95
142
|
|
624097 |
4
4
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
420
10.69
|
112
167
|
|
624096 |
12
12
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
686
17.43
|
305
454
|
|
662633 |
19
19
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
778
19.76
|
441
656
|
|
619488 |
3
3
|
12 AWG
12 AWG
|
7
7
|
30
0.76
|
|
|
424
10.79
|
121
181
|
|
607613 |
4
4
|
12 AWG
12 AWG
|
7
7
|
30
0.76
|
|
|
463
11.77
|
151
225
|
|
619086 |
2
2
|
10 AWG
10 AWG
|
7
7
|
30
0.76
|
|
|
452
11.49
|
125
186
|
|
618888 |
4
4
|
10 AWG
10 AWG
|
7
7
|
30
0.76
|
|
|
557
14.16
|
229
340
|
|
619090 |
5
5
|
10 AWG
10 AWG
|
7
7
|
30
0.76
|
|
|
591
15.02
|
282
420
|
|
619089 |
7
7
|
10 AWG
10 AWG
|
7
7
|
30
0.76
|
|
|
657
16.69
|
365
543
|
|
662655 |
9
9
|
10 AWG
10 AWG
|
7
7
|
30
0.76
|
|
|
765
19.44
|
507
754
|
|
606676 |
12
12
|
10 AWG
10 AWG
|
7
7
|
30
0.76
|
|
|
908
23.08
|
634
944
|
|
662652 |
19
19
|
10 AWG
10 AWG
|
7
7
|
30
0.76
|
|
|
1043
26.49
|
999
1487
|
|
619524 |
3
3
|
2 AWG
2 AWG
|
7
7
|
45
1.14
|
|
|
973
24.73
|
882
1313
|
|