Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of op- erating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. The ground is sized to 50% of the phase conductor with three separate bare grounds one in each interstecie between condutors. Silicone Free.
Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Inner Layer Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Outer Layer Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | |
More Options |
350 KCMIL
350 KCMIL
|
35
35
|
0.615
1.56
|
65
1.65
|
1.929
4.90
|
65
1.65
|
2.061
5.23
|
2081
3097
|
6300
2857.63
|
14.4
36.58
|
More Options |
600 KCMIL
600 KCMIL
|
41
41
|
0.812
2.06
|
80
2.03
|
2.402
6.10
|
80
2.03
|
2.568
6.52
|
3954
5884
|
10800
4898.79
|
18.0
45.72
|
More Options |
750 KCMIL
750 KCMIL
|
58
58
|
0.908
2.31
|
80
2.03
|
2.624
6.66
|
80
2.03
|
2.790
7.09
|
4071
6058
|
13500
6123.49
|
19.5
49.53
|
* Strand count meets minimum number per ASTM
Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | |
More Options |
350 KCMIL
350 KCMIL
|
0.050
0.07
|
0.062
0.09
|
0.012
0.02
|
0.040
0.06
|
More Options |
600 KCMIL
600 KCMIL
|
0.029
0.04
|
0.037
0.06
|
0.012
0.02
|
0.039
0.06
|
More Options |
750 KCMIL
750 KCMIL
|
0.024
0.04
|
0.031
0.05
|
0.011
0.02
|
0.038
0.06
|
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.