Southwire’s 2.4KV ARMOR-X® Type MC-HL are armored cables for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial or concrete encasement and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 130°C for emergency overload, 250°C for short circuit conditions, and -50°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503. Suitable for VFD application.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
890615 |
3
3
|
2 AWG
2 AWG
|
7
7
|
|
10
10
|
|
1536
39.01
|
1369
2037
|
|
890616 |
3
3
|
1/0 AWG
1/0 AWG
|
19
19
|
|
8
8
|
|
1666
42.32
|
1966
2925
|
|
890617 |
3
3
|
2/0 AWG
2/0 AWG
|
19
19
|
|
8
8
|
|
1796
45.62
|
2304
3428
|
|
890619 |
3
3
|
250 KCMIL
250 KCMIL
|
37
37
|
|
6
6
|
|
2166
55.02
|
3742
5569
|
|
890620 |
3
3
|
350 KCMIL
350 KCMIL
|
37
37
|
|
6
6
|
|
2448
62.18
|
5232
7786
|
|
890621 |
3
3
|
500 KCMIL
500 KCMIL
|
37
37
|
|
4
4
|
|
2828
71.83
|
6821
10151
|
|
890622 |
3
3
|
750 KCMIL
750 KCMIL
|
61
61
|
|
4
4
|
|
3158
80.21
|
9378
13956
|
|