Southwire’s 15KV ARMOR-X® are armored cables for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, 250°C for short circuit conditions, and -50°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
890663 |
3
3
|
2 AWG
2 AWG
|
7
7
|
|
6
6
|
|
2448
62.18
|
2630
3913
|
|
890664 |
3
3
|
1/0 AWG
1/0 AWG
|
19
19
|
|
4
4
|
|
2700
68.58
|
3358
4997
|
|
890665 |
3
3
|
2/0 AWG
2/0 AWG
|
19
19
|
|
4
4
|
|
2708
68.78
|
3650
5433
|
|
890666 |
3
3
|
4/0 AWG
4/0 AWG
|
19
19
|
|
3
3
|
|
2908
73.86
|
4781
7115
|
|
890667 |
3
3
|
250 KCMIL
250 KCMIL
|
37
37
|
|
2
2
|
|
3038
77.17
|
5345
7954
|
|
890668 |
3
3
|
350 KCMIL
350 KCMIL
|
37
37
|
|
2
2
|
|
3398
86.31
|
7098
10563
|
|
890669 |
3
3
|
500 KCMIL
500 KCMIL
|
37
37
|
|
1
1
|
|
3718
94.44
|
8562
12741
|
|
550439 |
3
3
|
750 KCMIL
750 KCMIL
|
58
58
|
|
1/0
1/0
|
|
4028
102.31
|
12039
17917
|
|