SPEC25010 CSA TECK 90 CU 1000V NON-SHIELDED XLPE POWER CABLE

1000V, Non-Shielded, XLPE Insulation, FT4, -40°C, HL (Hazardous Locations), 90°C

Download Category Specifications
PDF Excel Table

Application

Southwire's Single Conductor 1kV Teck 90 is a CSA approved armoured cable for Industrial and Commercial applications. FT4, -40C, HL, AG14 and 90°C rated for use in harsh Canadian environments. Rated for installation in cable trays, duct banks, direct burial, troughs, hazardous locations, continuous rigid cable supports, and concrete encaseable. CSA AG14 Acid Gas compliance. <ul> <li>-40°C - CSA Cold Bend and Impact Temperature</li> <li> -25°C - Min. Installation Temperature</li> <li> 90°C - Max. Continuous Operating Temperature</li> <li> 140°C for Emergency Overload Temperature</li> </ul>

Specifications

Select a set of products below for more information:
Cond. Size (AWG/Kcmil) Cond. Strands Diameter Over Conductor (in) (cm) Diameter Over Insulation (in) (cm) Insulation Thickness (mils) (mm) Diameter Over Shield (in) (cm) Ground (No. x AWG) Inner Jacket Thickness (mils) (mm) Diameter Over Armor (in) (cm) Drain Wire Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Approx. Weight (lbs/1000') (kgs/km) Max Pull Tension (lbs) (kg) Min. Bend Radius (in) (cm) Conduit Size (in) (cm)
597824
4/0 4/0
19 19
0.512 1.30
80 2.03
55 1.40
1.221 3.10
13x14 13x14
45 1.14
1.311 3.33
1271 1891
1692 767.48
9.1 23.11
586405
350 350
37 37
0.661 1.68
90 2.29
60 1.52
1.449 3.68
13x12 13x12
45 1.14
1.539 3.91
1935 2880
2800 1270.06
10.7 27.18
581915
500 500
37 37
0.789 2.00
90 2.29
60 1.52
1.574 4.00
17x12 17x12
55 1.40
1.684 4.28
2579 3838
4000 1814.37
11.7 29.72
576233
750 750
61 61
0.968 2.46
90 2.29
60 1.52
1.771 4.50
21x12 21x12
55 1.40
1.881 4.78
3572 5316
6000 2721.55
13.1 33.27
Cond. Size (AWG/Kcmil) DC Resistance @ 25C (ohms/1000') (ohms/km) AC Resistance @ 75C (ohms/1000') (ohms/km) Capacitive Reactance (Mohms x 1000ft) (Mohms x km) Inductive Reactance (ohms/1000') (ohms/km) Zero Sequence Impedance (ohms/1000') (ohms/1000') Positive Sequence Impedance (ohms/1000') (ohms/1000') Shield Short Circuit Current 6 Cycles (amps) Direct Buried Ampacity @ 90C (amps) Direct Buried Ampacity @ 105C (amps) In Duct Ampacity @ 90C (amps) In Duct Ampacity @ 105C (amps) In Air Ampacity @ 90C (amps) In Air Ampacity @ 105C (amps)
597824
4/0 4/0
0.051 0.08
0.062 0.09
0.041 0.06
586405
350 350
0.031 0.05
0.039 0.06
0.04 0.06
581915
500 500
0.022 0.03
0.029 0.04
0.039 0.06
576233
750 750
0.014 0.02
0.022 0.03
0.038 0.06

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 131 Type TECK 90 Cable
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • CSA AG14 - Acid Gas Compliance
  • ICEA S-96-659 (NEMA WC 71) 2001-5000 V Nonshielded Cables
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)

Construction

  1. Conductor: Class B stranded compressed copper in accordance with ASTM B3 and ASTM B8
  2. Insulation: XLPE (Cross Linked Polyethylene), Minimum Average Thickness: 4/0 = 0.08 inches (2.03 mm), 250 kcmil to 1000 kcmil = 0.090 inches (2.3 mm), 90°C
  3. Concentric Bonding Conductors: Class B, concentric bare copper wire serve
  4. Binder: Polypropylene Separator
  5. Inner Jacket: Black PVC, Minumum average thickness - 4/0 = 0.050" (1.27mm), 250 kcmil to 1000 kcmil = 0.060" (1.5 mm)
  6. Armor: Aluminum Interlocked Armour (AIA)
  7. Overall Jacket: Black PVC (optional colours available), Minimum Thickness: 4/0 to 400 kcmil = 0.050 inches (1.3 mm), 500 kcmil to 1000 kcmil = 0.060 inches (1.5 mm)