Southwire's 35kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Cond. Size (AWG/Kcmil) | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Ground (No. x AWG) | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Drain Wire | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Conduit Size (in) (cm) | |
653019 |
2/0
2/0
|
19
19
|
0.405
1.03
|
1.284
3.26
|
420
10.67
|
1.344
3.41
|
|
125
3.18
|
3.566
9.06
|
|
85
2.16
|
3.736
9.49
|
5789
8615
|
3194
1448.77
|
26.2
66.55
|
|
Cond. Size (AWG/Kcmil) | DC Resistance @ 25C (ohms/1000') (ohms/km) | AC Resistance @ 75C (ohms/1000') (ohms/km) | Capacitive Reactance (Mohms x 1000ft) (Mohms x km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles (amps) | Direct Buried Ampacity @ 90C (amps) | Direct Buried Ampacity @ 105C (amps) | In Duct Ampacity @ 90C (amps) | In Duct Ampacity @ 105C (amps) | In Air Ampacity @ 90C (amps) | In Air Ampacity @ 105C (amps) | |
653019 |
2/0
2/0
|
0.081
0.12
|
0.102
0.15
|
0.075
0.11
|
0.05
0.07
|
0.436 + j0.262
0.436 + j0.262
|
0.102 + j0.050
0.102 + j0.050
|
4192
4192
|
290
290
|
|
|
|
265
265
|
|