SPEC45301 CU 600/1000V XLPE Insulation AIA PVC Jacket XHHW-2. CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free

Type MC Power Cable 600Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. Silicone Free.

Download Category Specifications
PDF Excel Table

Application

Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Silicone Free.

Specifications

Select a set of products below for more information:
Cond. Size (AWG/Kcmil) Cond. Strands Diameter Over Conductor (in) (cm) Diameter Over Insulation (in) (cm) Insulation Thickness (mils) (mm) Diameter Over Shield (in) (cm) Ground (No. x AWG) Inner Jacket Thickness (mils) (mm) Diameter Over Armor (in) (cm) Drain Wire Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Approx. Weight (lbs/1000') (kgs/km) Max Pull Tension (lbs) (kg) Min. Bend Radius (in) (cm) Conduit Size (in) (cm)
606939
8 8
7 7
0.141 0.36
45 1.14
0.721 1.83
50 1.27
0.821 2.09
404 601
396 179.62
5.7 14.48
606947
6 6
7 7
0.177 0.45
45 1.14
0.788 2.00
50 1.27
0.888 2.26
545 811
629 285.31
6.2 15.75
606954
4 4
7 7
0.225 0.57
45 1.14
0.898 2.28
50 1.27
0.998 2.53
713 1061
1001 454.05
7.0 17.78
560466
2 2
7 7
0.282 0.72
45 1.14
1.019 2.59
50 1.27
1.119 2.84
1046 1557
1592 722.12
7.8 19.81
550801
1 1
19 19
0.322 0.82
55 1.40
1.151 2.92
50 1.27
1.251 3.18
1264 1881
2008 910.81
8.8 22.35
560474
1/0 1/0
19 19
0.361 0.92
55 1.40
1.233 3.13
50 1.27
1.333 3.39
1499 2231
2534 1149.40
9.3 23.62
560482
2/0 2/0
19 19
0.405 1.03
55 1.40
1.328 3.37
50 1.27
1.428 3.63
1816 2703
3194 1448.77
10.0 25.40
890339
3/0 3/0
19 19
0.456 1.16
55 1.40
1.436 3.65
50 1.27
1.536 3.90
2256 3357
4027 1826.61
10.8 27.43
383679
4/0 4/0
19 19
0.512 1.30
55 1.40
1.631 4.14
60 1.52
1.751 4.45
2786 4146
5078 2303.34
12.3 31.24
601377
250 250
37 37
0.558 1.42
65 1.65
1.769 4.49
60 1.52
1.889 4.80
3379 5029
6000 2721.55
13.2 33.53
383646
350 350
37 37
0.661 1.68
65 1.65
1.983 5.04
60 1.52
2.103 5.34
4551 6773
8400 3810.17
14.7 37.34
380618
500 500
37 37
0.789 2.00
65 1.65
2.253 5.72
75 1.91
2.403 6.10
6180 9197
12000 5443.10
16.8 42.67
890391
600 600
61 61
0.865 2.20
80 2.03
2.507 6.37
75 1.91
2.657 6.75
7604 11316
14400 6531.72
18.6 47.24
890405
750 750
61 61
0.968 2.46
80 2.03
2.758 7.01
75 1.91
2.908 7.39
9227 13731
18000 8164.66
20.4 51.82
Cond. Size (AWG/Kcmil) DC Resistance @ 25C (ohms/1000') (ohms/km) AC Resistance @ 75C (ohms/1000') (ohms/km) Capacitive Reactance (Mohms x 1000ft) (Mohms x km) Inductive Reactance (ohms/1000') (ohms/km) Zero Sequence Impedance (ohms/1000') (ohms/1000') Positive Sequence Impedance (ohms/1000') (ohms/1000') Shield Short Circuit Current 6 Cycles (amps) Direct Buried Ampacity @ 90C (amps) Direct Buried Ampacity @ 105C (amps) In Duct Ampacity @ 90C (amps) In Duct Ampacity @ 105C (amps) In Air Ampacity @ 90C (amps) In Air Ampacity @ 105C (amps)
606939
8 8
0.653 0.97
0.786 1.17
0.033 0.05
0.052 0.08
606947
6 6
0.411 0.61
0.495 0.74
0.027 0.04
0.051 0.08
606954
4 4
0.258 0.38
0.31 0.46
0.022 0.03
0.048 0.07
560466
2 2
0.162 0.24
0.195 0.29
0.018 0.03
0.045 0.07
550801
1 1
0.128 0.19
0.154 0.23
0.019 0.03
0.046 0.07
560474
1/0 1/0
0.102 0.15
0.122 0.18
0.017 0.03
0.044 0.07
560482
2/0 2/0
0.081 0.12
0.097 0.14
0.016 0.02
0.043 0.06
890339
3/0 3/0
0.064 0.10
0.078 0.12
0.014 0.02
0.042 0.06
383679
4/0 4/0
0.051 0.08
0.062 0.09
0.013 0.02
0.041 0.06
601377
250 250
0.043 0.06
0.053 0.08
0.014 0.02
0.041 0.06
383646
350 350
0.031 0.05
0.039 0.06
0.012 0.02
0.04 0.06
380618
500 500
0.022 0.03
0.029 0.04
0.01 0.01
0.039 0.06
890391
600 600
0.018 0.03
0.025 0.04
0.011 0.02
0.039 0.06
890405
750 750
0.014 0.02
0.022 0.03
0.01 0.01
0.038 0.06

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)

Construction

  1. Conductor: Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation: Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor: Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  4. Filler: Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder: Polypropylene tape
  6. Armor: Aluminum Interlocked Armor (AIA)
  7. Overall Jacket: Polyvinyl Chloride (PVC) Jacket