HS285® Ultra-High Strength ACSS TW Conductor

Download Category Specifications:
PDF Excel Table

Application

HS285 is the most popular high temperature low sag (HTLS) conductor in use today because of its versatility and strength. The multipurpose conductor is up to 21 percent stronger than standard ACSS, reducing sag while allowing for additional line capacity. Developed at Southwire’s D.B. Cofer Technology Center, HS285 has been proven in the field for capacity up to 95 percent higher than ACSR, lowering reconductoring costs. HS285 can be strung tighter to operate with more clearance at higher temperatures. It also allows for easy installation using existing rights of way, structures and methods.

Specifications

measurement
imperial metric
Select a set of products below for more information:
Conductor
No. of Conductors Size (AWG or kcmil) No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity
662879 1 1 477 KCMIL 477 KCMIL 0 0 820 20.83 746 1111
619645 1 1 565.3 KCMIL 565.3 KCMIL 0 0 860 21.84 776 1154
663085 1 1 666.6 KCMIL 666.6 KCMIL 0 0 913 23.19 856 1274
614382 1 1 768.2 KCMIL 768.2 KCMIL 0 0 977 24.82 987 1469
613870 1 1 795 KCMIL 795 KCMIL 20 20 1010 25.65 1091 1624
616068 1 1 900 KCMIL 900 KCMIL 0 0 1055 26.80 1185 1763
613431 1 1 954 KCMIL 954 KCMIL 20 20 1080 27.43 1224 1822
614691 1 1 959.6 KCMIL 959.6 KCMIL 0 0 1110 28.20 1317 1959
614201 1 1 1113 KCMIL 1113 KCMIL 0 0 1278 32.46 890 1325
619995 1 1 1192.5 KCMIL 1192.5 KCMIL 0 0 1225 31.12 1531 2278
613868 1 1 1233.6 KCMIL 1233.6 KCMIL 38 38 1245 31.62 1583 2357
616610 1 1 1351.5 KCMIL 1351.5 KCMIL 42 42 1300 33.02 1732 2577
662837 1 1 1590 KCMIL 1590 KCMIL 0 0 1410 35.81 2038 3033
661919 1 1 2627.3 KCMIL 2627.3 KCMIL 0 0 1760 44.71 3062 4557
619103 1 1 636 null 636 null 0 0 909 23.09 873 1299
604522 1 1 477 KCMIL 477 KCMIL 18 18 790 20.07 656 976

Standards & References

Construction

ACSS is a composite concentric-lay-stranded conductor. Steel strands form the central core of the conductor with one or more layers of 63% minimum average conductivity aluminum 1350-0 wire stranded around it. The steel core carries most or all of the mechanical load of the conductor due to the “0” (fully annealed or soft) temper aluminum. Ultra high-strength steel core wires are protected from corrosion by Galfan® , zinc-5% aluminum-mischmetal alloy coating.

  • Shaped Wire Concentric-Lay Compact Aluminum Conductors Steel Supported (ACSS/TW) (HS285)