SPEC: 22061

RW90 Copper Circuit Sizes (14, 12 & 10 AWG)

Copper Conductor, 600V, 90°C MAX, -40°C MIN. All Sizes and Colors are Sunlight Resistant.

Download Category Specifications
PDF Excel Table

Application & Features

Single copper conductor with low temperature, moisture resisting XLPE (cross linked polyethylene) insulation. All sizes are Sunlight Resistant in all colors and packaging. This product meets the current RoHS requirements. No lead is added or used in manufacturing.

Specifications

Select a set of products below for more information:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
14 AWG 14 AWG
1 1
Solid Solid
0.064 0.16
30 0.76
0.128 0.33
12 18
16 24
More Options
14 AWG 14 AWG
1 1
7 7
0.070 0.18
30 0.76
0.135 0.34
12 18
17 25
More Options
12 AWG 12 AWG
1 1
Solid Solid
0.080 0.20
30 0.76
0.144 0.37
19 28
24 36
More Options
12 AWG 12 AWG
1 1
7 7
0.088 0.22
30 0.76
0.153 0.39
20 30
25 37
More Options
10 AWG 10 AWG
1 1
Solid Solid
0.101 0.26
30 0.76
0.165 0.42
31 46
37 55
More Options
10 AWG 10 AWG
1 1
7 7
0.113 0.29
30 0.76
0.177 0.45
32 48
39 58

†Ampacities derived from the 2015 Canadian Electrical Code - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C. - Table 2 - for Cable in Conduit. Not more than 3 aluminum conductors in a conduit and based on an ambient temperature of 30°C.

Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
14 AWG 14 AWG
1 1
0.500 1.27
32 14.51
2.631 3.92
3.170 4.72
0.058 0.09
20 20
25 25
More Options
14 AWG 14 AWG
1 1
0.500 1.27
32 14.51
2.631 3.92
3.170 4.72
0.058 0.09
20 20
25 25
More Options
12 AWG 12 AWG
1 1
0.600 1.52
52 23.59
1.662 2.47
2.002 2.98
0.054 0.08
25 25
30 30
More Options
12 AWG 12 AWG
1 1
0.600 1.52
52 23.59
1.662 2.47
2.002 2.98
0.054 0.08
25 25
30 30
More Options
10 AWG 10 AWG
1 1
0.700 1.78
83 37.65
1.040 1.55
1.253 1.86
0.050 0.07
35 35
40 40
More Options
10 AWG 10 AWG
1 1
0.700 1.78
83 37.65
1.040 1.55
1.253 1.86
0.050 0.07
35 35
40 40

* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

Size (Strand) Color Stock Number
14 (Solid) 14 (Solid)
BK BK
956110
14 (Solid) 14 (Solid)
RD RD
956177
14 (Solid) 14 (Solid)
WE WE
956144
14 (Solid) 14 (Solid)
BN BN
956250
14 (Solid) 14 (Solid)
YW YW
956276
14 (Solid) 14 (Solid)
GN GN
956201
14 (Solid) 14 (Solid)
BE BE
956235
14 (Solid) 14 (Solid)
OE OE
557917
14 (7) 14 (7)
GN GN
955617
14 (7) 14 (7)
RD RD
955245
14 (7) 14 (7)
BE BE
955666
14 (7) 14 (7)
YW YW
955708
14 (7) 14 (7)
BK BK
951731
14 (7) 14 (7)
OE OE
557924
14 (7) 14 (7)
BN BN
955682
12 (Solid) 12 (Solid)
OE OE
557861
12 (Solid) 12 (Solid)
BK BK
956102
12 (Solid) 12 (Solid)
RD RD
956169
12 (Solid) 12 (Solid)
BE BE
956227
12 (Solid) 12 (Solid)
BN BN
956243
12 (Solid) 12 (Solid)
YW YW
956268
12 (Solid) 12 (Solid)
WE WE
956136
12 (Solid) 12 (Solid)
GN GN
956193
12 (7) 12 (7)
BK BK
951749
12 (7) 12 (7)
GN GN
955609
12 (7) 12 (7)
BE BE
955658
12 (7) 12 (7)
BN BN
955674
12 (7) 12 (7)
RD RD
955237
12 (7) 12 (7)
OE OE
557923
12 (7) 12 (7)
YW YW
955690
10 (Solid) 10 (Solid)
RD RD
956151
10 (Solid) 10 (Solid)
OE OE
557930
10 (Solid) 10 (Solid)
BK BK
956094
10 (Solid) 10 (Solid)
BN BN
557929
10 (Solid) 10 (Solid)
WE WE
956128
10 (Solid) 10 (Solid)
GN GN
956185
10 (Solid) 10 (Solid)
BE BE
956219
10 (7) 10 (7)
BK BK
951756
10 (7) 10 (7)
BE BE
955641
10 (7) 10 (7)
OE OE
557921
10 (7) 10 (7)
GN GN
955591
10 (7) 10 (7)
BN BN
557920
10 (7) 10 (7)
YW YW
557922
10 (7) 10 (7)
RD RD
955229

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • CSA SUN RES - for Sunlight Resistant rating

Construction

  1. Conductor: Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation: Cross Linked Polyethylene (XLPE)