Southwire's SIMpull ® Copper RW90 is for open wiring and use in raceways (except cabletroughs and ventilated flexible cableways) in dry or wet locations. For open wiring exposed to the weather. Minimum recommended installation temperature minus 40°C (with suitable handling procedures). Maximum conductor temperature 90°C.
Conductor | Allowable Ampacities | ||||||||
Size (AWG or kcmil) (mm2) | No. of Strands | Nom. OD (mils) (mm) | Insulation Thickness (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity at 75°C Open Air | Allowable Ampacity at 90°C Open Air | Allowable Ampacity at 75°C Cable in Conduit | Allowable Ampacity at 90°C Cable in Conduit | |
557924 |
14 AWG
14 AWG
|
7
7
|
134
3.42
|
30
0.76
|
17
26
|
30
30
|
35
35
|
20
20
|
25
25
|
557861 |
12 AWG
12 AWG
|
1
1
|
144
3.68
|
30
0.76
|
25
37
|
35
35
|
40
40
|
25
25
|
30
30
|
585274 |
12 AWG
12 AWG
|
1
1
|
422
10.73
|
30
0.76
|
73
109
|
35
35
|
40
40
|
25
25
|
30
30
|
557920 |
10 AWG
10 AWG
|
7
7
|
177
4.50
|
30
0.76
|
39
58
|
50
50
|
55
55
|
35
35
|
40
40
|
955203 |
8 AWG
8 AWG
|
7
7
|
238
6.05
|
45
1.14
|
65
97
|
70
70
|
80
80
|
50
50
|
55
55
|
580482 |
6 AWG
6 AWG
|
7
7
|
274
6.96
|
45
1.14
|
98
146
|
95
95
|
105
105
|
65
65
|
75
75
|
552008 |
4 AWG
4 AWG
|
7
7
|
321
8.15
|
45
1.14
|
150
223
|
125
125
|
140
140
|
85
85
|
95
95
|
552003 |
3 AWG
3 AWG
|
7
7
|
348
8.84
|
45
1.14
|
186
276
|
145
145
|
165
165
|
100
100
|
115
115
|
552001 |
2 AWG
2 AWG
|
7
7
|
379
9.63
|
45
1.14
|
231
344
|
170
170
|
190
190
|
115
115
|
130
130
|
577425 |
1 AWG
1 AWG
|
19
19
|
438
11.13
|
55
1.40
|
292
435
|
195
195
|
220
220
|
130
130
|
145
145
|
573677 |
1/0 AWG
1/0 AWG
|
19
19
|
478
12.14
|
55
1.40
|
364
541
|
230
230
|
260
260
|
150
150
|
170
170
|
559411 |
2/0 AWG
2/0 AWG
|
19
19
|
522
13.26
|
55
1.40
|
453
674
|
265
265
|
300
300
|
175
175
|
195
195
|
557919 |
3/0 AWG
3/0 AWG
|
19
19
|
570
14.48
|
55
1.40
|
564
840
|
310
310
|
350
350
|
200
200
|
225
225
|
559562 |
4/0 AWG
4/0 AWG
|
19
19
|
626
15.90
|
55
1.40
|
707
1052
|
360
360
|
405
405
|
230
230
|
260
260
|
575228 |
250 KCMIL
250 KCMIL
|
37
37
|
680
17.27
|
65
1.65
|
828
1232
|
405
405
|
455
455
|
255
255
|
290
290
|
577715 |
350 KCMIL
350 KCMIL
|
37
37
|
779
19.79
|
65
1.65
|
1145
1703
|
505
505
|
570
570
|
310
310
|
350
350
|
581547 |
500 KCMIL
500 KCMIL
|
37
37
|
904
22.96
|
65
1.65
|
1618
2408
|
620
620
|
700
700
|
380
380
|
430
430
|
586441 |
600 KCMIL
600 KCMIL
|
61
61
|
1010
25.65
|
80
2.03
|
1948
2900
|
690
690
|
780
780
|
420
420
|
475
475
|
951921 |
1000 KCMIL
1000 KCMIL
|
61
61
|
1287
32.69
|
80
2.03
|
3232
4810
|
935
935
|
1055
1055
|
545
545
|
615
615
|
Southwire’s SIMpull ® RW90 cables meet or exceed the following requirements:
Single copper conductor with low temperature" moisture resisting XLPE (cross linked polyethylene) insulation.