Southwire SIMpull® THHN/THWN-2 copper conductors are primarily used in conduit and cable trays for services, feeders, and branch circuits in commercial or industrial applications as specified in the National Electrical Code® and other applicable codes and standards. Voltage for all applications is 600 volts. SIMpull® THHN/THWN-2 copper conductors are designed to be installed without the application of a pulling lubricant. These conductors have multiple ratings depending upon the product application. Allowable temperatures are as follows:
- THHN or T90 Nylon- Dry locations not to exceed 90°C
- THWN-2- Wet or dry locations not to exceed 90° C or locations not to exceed 75°C when exposed to oil
- TWN75- Wet locations not to exceed 75°C
- MTW- Wet locations or when exposed to oil at temperatures not to exceed 60°C or dry locations not to exceed 90°C (with ampacity limited to that for 75°C conductor temperature per NFPA 79)
- AWM- Dry locations not to exceed 105°C only when rated and used as appliance wiring material
FEATURES
- Sunlight resistant #8 AWG and larger
- Gasoline and Oil Resistant II
- CT Rated 1/0 AWG and Larger
- VW-1 All Sizes
- FT-1 All Sizes
- AWM- Sizes 14 through 6 AWG
- MTW- Stranded Constructions Only
- RoHS Compliant
- LEED v4.1 Materials & Resources Credit MRc6; PBT (Lead Content Below 300 ppm Threshold)
Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Copper Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
More Options |
8 AWG
8 AWG
|
1
1
|
19
19
|
0.143
0.36
|
31
0.79
|
6
0.15
|
0.217
0.55
|
50
74
|
63
94
|
More Options |
6 AWG
6 AWG
|
1
1
|
19
19
|
0.179
0.45
|
31
0.79
|
6
0.15
|
0.253
0.64
|
81
121
|
95
141
|
More Options |
4 AWG
4 AWG
|
1
1
|
19
19
|
0.226
0.57
|
41
1.04
|
7
0.18
|
0.322
0.82
|
128
190
|
153
228
|
More Options |
3 AWG
3 AWG
|
1
1
|
19
19
|
0.254
0.65
|
41
1.04
|
7
0.18
|
0.350
0.89
|
162
241
|
189
281
|
More Options |
2 AWG
2 AWG
|
1
1
|
19
19
|
0.286
0.73
|
41
1.04
|
7
0.18
|
0.382
0.97
|
204
304
|
235
350
|
More Options |
1 AWG
1 AWG
|
1
1
|
19
19
|
0.322
0.82
|
52
1.32
|
8
0.20
|
0.439
1.12
|
258
384
|
301
448
|
More Options |
1/0 AWG
1/0 AWG
|
1
1
|
19
19
|
0.361
0.92
|
52
1.32
|
8
0.20
|
0.480
1.22
|
326
485
|
374
557
|
More Options |
2/0 AWG
2/0 AWG
|
1
1
|
19
19
|
0.405
1.03
|
52
1.32
|
8
0.20
|
0.524
1.33
|
410
610
|
464
691
|
More Options |
3/0 AWG
3/0 AWG
|
1
1
|
19
19
|
0.456
1.16
|
52
1.32
|
8
0.20
|
0.574
1.46
|
518
771
|
578
860
|
More Options |
4/0 AWG
4/0 AWG
|
1
1
|
19
19
|
0.512
1.30
|
52
1.32
|
8
0.20
|
0.627
1.59
|
653
972
|
719
1070
|
More Options |
250 KCMIL
250 KCMIL
|
1
1
|
37
37
|
0.558
1.42
|
62
1.57
|
9
0.23
|
0.684
1.74
|
771
1147
|
844
1256
|
More Options |
300 KCMIL
300 KCMIL
|
1
1
|
37
37
|
0.610
1.55
|
62
1.57
|
9
0.23
|
0.753
1.91
|
926
1378
|
1016
1512
|
More Options |
350 KCMIL
350 KCMIL
|
1
1
|
37
37
|
0.661
1.68
|
62
1.57
|
9
0.23
|
0.803
2.04
|
1080
1607
|
1180
1756
|
More Options |
400 KCMIL
400 KCMIL
|
1
1
|
37
37
|
0.705
1.79
|
62
1.57
|
9
0.23
|
0.848
2.15
|
1235
1838
|
1341
1996
|
More Options |
500 KCMIL
500 KCMIL
|
1
1
|
37
37
|
0.789
2.00
|
62
1.57
|
9
0.23
|
0.931
2.36
|
1543
2296
|
1662
2473
|
More Options |
600 KCMIL
600 KCMIL
|
1
1
|
61
61
|
0.865
2.20
|
70
1.78
|
10
0.25
|
1.030
2.62
|
1852
2756
|
1992
2964
|
More Options |
750 KCMIL
750 KCMIL
|
1
1
|
61
61
|
0.968
2.46
|
70
1.78
|
10
0.25
|
1.132
2.88
|
2315
3445
|
2470
3676
|
More Options |
1000 KCMIL
1000 KCMIL
|
1
1
|
61
61
|
1.117
2.84
|
70
1.78
|
10
0.25
|
1.281
3.25
|
3087
4594
|
3264
4857
|
Cond. Size | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
More Options |
8 AWG
8 AWG
|
1
1
|
0.9
2.29
|
132
59.87
|
0.653
0.97
|
0.786
1.17
|
0.052
0.08
|
50
50
|
55
55
|
More Options |
6 AWG
6 AWG
|
1
1
|
1.0
2.54
|
209
94.80
|
0.411
0.61
|
0.495
0.74
|
0.051
0.08
|
65
65
|
75
75
|
More Options |
4 AWG
4 AWG
|
1
1
|
1.3
3.30
|
333
151.05
|
0.258
0.38
|
0.310
0.46
|
0.048
0.07
|
85
85
|
95
95
|
More Options |
3 AWG
3 AWG
|
1
1
|
1.4
3.56
|
420
190.51
|
0.205
0.31
|
0.246
0.37
|
0.047
0.07
|
100
100
|
115
115
|
More Options |
2 AWG
2 AWG
|
1
1
|
1.5
3.81
|
530
240.40
|
0.162
0.24
|
0.195
0.29
|
0.045
0.07
|
115
115
|
130
130
|
More Options |
1 AWG
1 AWG
|
1
1
|
1.8
4.57
|
669
303.45
|
0.128
0.19
|
0.154
0.23
|
0.046
0.07
|
130
130
|
145
145
|
More Options |
1/0 AWG
1/0 AWG
|
1
1
|
1.9
4.83
|
844
382.83
|
0.102
0.15
|
0.122
0.18
|
0.044
0.07
|
150
150
|
170
170
|
More Options |
2/0 AWG
2/0 AWG
|
1
1
|
2.1
5.33
|
1064
482.62
|
0.081
0.12
|
0.097
0.14
|
0.043
0.06
|
175
175
|
195
195
|
More Options |
3/0 AWG
3/0 AWG
|
1
1
|
2.3
5.84
|
1342
608.72
|
0.064
0.10
|
0.078
0.12
|
0.042
0.06
|
200
200
|
225
225
|
More Options |
4/0 AWG
4/0 AWG
|
1
1
|
2.5
6.35
|
1692
767.48
|
0.051
0.08
|
0.062
0.09
|
0.041
0.06
|
230
230
|
260
260
|
More Options |
250 KCMIL
250 KCMIL
|
1
1
|
2.7
6.86
|
2000
907.18
|
0.043
0.06
|
0.053
0.08
|
0.041
0.06
|
255
255
|
290
290
|
More Options |
300 KCMIL
300 KCMIL
|
1
1
|
3.0
7.62
|
2400
1088.62
|
0.036
0.05
|
0.045
0.07
|
0.041
0.06
|
285
285
|
320
320
|
More Options |
350 KCMIL
350 KCMIL
|
1
1
|
3.2
8.13
|
2800
1270.06
|
0.031
0.05
|
0.039
0.06
|
0.040
0.06
|
310
310
|
350
350
|
More Options |
400 KCMIL
400 KCMIL
|
1
1
|
3.4
8.64
|
3200
1451.49
|
0.027
0.04
|
0.035
0.05
|
0.040
0.06
|
335
335
|
380
380
|
More Options |
500 KCMIL
500 KCMIL
|
1
1
|
3.7
9.40
|
4000
1814.37
|
0.022
0.03
|
0.029
0.04
|
0.039
0.06
|
380
380
|
430
430
|
More Options |
600 KCMIL
600 KCMIL
|
1
1
|
5.2
13.21
|
4800
2177.24
|
0.018
0.03
|
0.025
0.04
|
0.039
0.06
|
420
420
|
475
475
|
More Options |
750 KCMIL
750 KCMIL
|
1
1
|
5.7
14.48
|
6000
2721.55
|
0.014
0.02
|
0.022
0.03
|
0.038
0.06
|
475
475
|
535
535
|
More Options |
1000 KCMIL
1000 KCMIL
|
1
1
|
6.4
16.26
|
8000
3628.74
|
0.011
0.02
|
0.018
0.03
|
0.037
0.06
|
545
545
|
615
615
|
* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center
Size (Strand) | Black | Red | Blue | White | Brown | Orange | Yellow | Gray | Green | Purple |
8 (19)
8 (19)
|
||||||||||
6 (19)
6 (19)
|
||||||||||
4 (19)
4 (19)
|
||||||||||
3 (19)
3 (19)
|
||||||||||
2 (19)
2 (19)
|
||||||||||
1 (19)
1 (19)
|
||||||||||
1/0 (19)
1/0 (19)
|
||||||||||
2/0 (19)
2/0 (19)
|
||||||||||
3/0 (19)
3/0 (19)
|
||||||||||
4/0 (19)
4/0 (19)
|
||||||||||
250 (37)
250 (37)
|
||||||||||
300 (37)
300 (37)
|
||||||||||
350 (37)
350 (37)
|
||||||||||
400 (37)
400 (37)
|
||||||||||
500 (37)
500 (37)
|
||||||||||
600 (61)
600 (61)
|
||||||||||
750 (61)
750 (61)
|
||||||||||
1000 (61)
1000 (61)
|
|
|
|
|
|
Size (Strand) | Pink | Tan | White/Red | Gray/Purple | Gray/Orange | Gray/Yellow | Gray/Brown | Green/Yellow | White/Blue | White/Black |
8 (19)
8 (19)
|
|
|
|
|
|
|
|
|
||
6 (19)
6 (19)
|
|
|
|
|
|
|
|
|
||
4 (19)
4 (19)
|
597980
597980
|
597979
597979
|
|
|
|
|
|
|
|
|
3 (19)
3 (19)
|
597978
597978
|
597977
597977
|
|
|
|
|
|
679383
679383
|
|
|
2 (19)
2 (19)
|
|
|
|
|
|
|
|
|
|
|
1 (19)
1 (19)
|
578284
578284
|
578285
578285
|
|
|
|
|
|
679438
679438
|
|
|
1/0 (19)
1/0 (19)
|
|
|
|
|
|
|
|
|||
2/0 (19)
2/0 (19)
|
|
|
|
|
|
|
|
|||
3/0 (19)
3/0 (19)
|
|
677828
677828
|
|
|
|
679380
679380
|
|
|
||
4/0 (19)
4/0 (19)
|
|
|
|
|
|
|
|
|||
250 (37)
250 (37)
|
|
|
|
|
646952
646952
|
|
|
|||
300 (37)
300 (37)
|
|
|
|
|
|
|
|
|
||
350 (37)
350 (37)
|
|
|
|
|
679458
679458
|
|
|
|||
400 (37)
400 (37)
|
|
|
|
|
|
|
|
|||
500 (37)
500 (37)
|
|
|
|
|
|
|
|
|
||
600 (61)
600 (61)
|
|
|
|
|
|
|
|
|||
750 (61)
750 (61)
|
597954
597954
|
597955
597955
|
|
|
|
|
|
|
|
|
1000 (61)
1000 (61)
|
|
|
|
|
|
|
|
|
|
|