600V AMERICAN MUSTANG® SOOW Cord with Yellow Jacket 105°C

600V AMERICAN MUSTANG® SOOW Cord with Yellow Jacket 105°C

600V, 105°C Flexible Cord. Heat, Moisture and Oil Resistant EPDM Rubber Insulation and Heat, Moisture and Oil Resistant Flexible CPE Jacket, UL/CSA Listed.
Download Category Specifications:
PDF Excel Table

Application

Southwire Type SOOW Flexible Cords UL/ CSA listed are permitted for use as specified by Article 400 and related articles of the 2014 National Electrical Code. The cable is rated -40°C to 105°C, water, oil, and weather resistant. Southwire Type SOOW Flexible Cords are designed for extra hard usage on industrial equipment, heavy tools, battery chargers, portable lights, welding leads, marine dockside power, power extensions and mining applications.

Specifications

measurement
imperial metric
Select a set of products below for more information:
Conductor
Size (AWG or kcmil) No. of Conductors No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity Nom. DC Resistance (Conductor) Conductor Colors
570214 16 AWG 16 AWG 2 2 65 65 370 9.40 75 111 13 13 4.05 4.05 BLACK/WHITE BLACK/WHITE
630730 16 AWG 16 AWG 3 3 26 26 390 9.91 91 135 13 13 4.05 4.05 BLACK/WHITE/GREEN BLACK/WHITE/GREEN
630727 16 AWG 16 AWG 4 4 26 26 415 10.54 107 159 10 10 4.05 4.05 BLACK/WHITE/RED/GREEN BLACK/WHITE/RED/GREEN
598334 14 AWG 14 AWG 2 2 41 41 513 13.03 134 199 18 18 2.55 2.55 BLACK/WHITE BLACK/WHITE
630721 14 AWG 14 AWG 3 3 41 41 525 13.34 158 235 18 18 2.55 2.55 BLACK/WHITE/GREEN BLACK/WHITE/GREEN
596981 14 AWG 14 AWG 4 4 41 41 565 14.35 193 287 15 15 2.55 2.55 BLACK/WHITE/RED/GREEN BLACK/WHITE/RED/GREEN
595327 12 AWG 12 AWG 3 3 65 65 609 15.47 211 315 25 25 1.61 1.61 BLACK/WHITE/GREEN BLACK/WHITE/GREEN
630722 12 AWG 12 AWG 4 4 65 65 668 16.97 274 408 20 20 1.61 1.61 BLACK/WHITE/RED/GREEN BLACK/WHITE/RED/GREEN
630724 10 AWG 10 AWG 3 3 104 104 655 16.64 281 418 30 30 0.98 0.98 BLACK/WHITE/GREEN BLACK/WHITE/GREEN
630725 10 AWG 10 AWG 4 4 104 104 710 18.03 337 501 25 25 0.98 0.98 BLACK/WHITE/RED/GREEN BLACK/WHITE/RED/GREEN

Standards & References

  • UL 62
  • CSA Standard 22.2 No. 49
  • NEC 400
  • NEC 501.140 Class I Division 2
  • Passes CSA FT2 Flame Test
  • MSHA
  • Federal and Military Specification JC-580B
  • RoHS-2 (European Directive 2011/65/EU )

Construction

  • Conductors: Class K stranded bare copper per ASTM B-174
  • Insulation: EPDM
  • Jacket: Yellow CPE (Other colors available upon request)

Resources

There are no downloadable resources for this product.