Southwire’s Machine Flex® power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 150°C for short circuit conditions. 1/0 AWG & larger rated for CT use.
Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Inner Layer Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | |
More Options |
4/0 AWG
4/0 AWG
|
1.0
1.0
|
2109
2109
|
0.550
1.40
|
60
1.52
|
0.664
1.69
|
746
1110
|
More Options |
250 KCMIL
250 KCMIL
|
1.0
1.0
|
627
627
|
0.605
1.54
|
70
1.78
|
0.747
1.90
|
857
1275
|
More Options |
350 KCMIL
350 KCMIL
|
1.0
1.0
|
893
893
|
0.670
1.70
|
60
1.52
|
0.812
2.06
|
1172
1744
|
More Options |
500 KCMIL
500 KCMIL
|
1.0
1.0
|
1221
1221
|
0.858
2.18
|
70
1.78
|
0.998
2.53
|
1641
2442
|
More Options |
600 KCMIL
600 KCMIL
|
1.0
1.0
|
1480
1480
|
0.963
2.45
|
70
1.78
|
1.127
2.86
|
2033
3025
|
More Options |
750 KCMIL
750 KCMIL
|
1.0
1.0
|
1850
1850
|
1.094
2.78
|
80
2.03
|
1.258
3.20
|
2569
3823
|
More Options |
300 KCMIL
300 KCMIL
|
1.0
1.0
|
741
741
|
0.638
1.62
|
70
1.78
|
0.780
1.98
|
1024
1524
|
Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
More Options |
4/0 AWG
4/0 AWG
|
0.057
0.08
|
0.069
0.10
|
0.041
0.06
|
1692
767.48
|
2.6
6.60
|
230
230
|
260
260
|
More Options |
250 KCMIL
250 KCMIL
|
0.047
0.07
|
0.057
0.08
|
0.041
0.06
|
2000
907.18
|
2.9
7.37
|
255
255
|
290
290
|
More Options |
350 KCMIL
350 KCMIL
|
0.033
0.05
|
0.042
0.06
|
0.040
0.06
|
2800
1270.06
|
3.2
8.13
|
310
310
|
350
350
|
More Options |
500 KCMIL
500 KCMIL
|
0.023
0.03
|
0.031
0.05
|
0.039
0.06
|
4000
1814.37
|
3.9
9.91
|
380
380
|
430
430
|
More Options |
600 KCMIL
600 KCMIL
|
0.019
0.03
|
0.027
0.04
|
0.039
0.06
|
4800
2177.24
|
5.6
14.22
|
420
420
|
475
475
|
More Options |
750 KCMIL
750 KCMIL
|
0.016
0.02
|
0.024
0.04
|
0.038
0.06
|
6000
2721.55
|
6.2
15.75
|
475
475
|
535
535
|
More Options |
300 KCMIL
300 KCMIL
|
0.039
0.06
|
0.048
0.07
|
0.041
0.06
|
2400
1088.62
|
3.1
7.87
|
285
285
|
320
320
|
† Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
† Ampacities have been adjusted for more than Three Current-Carrying Conductors.
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
Size (Strand) | Black | Red | Brown | Orange | Yellow | Gray | Green | Pink | Purple | Tan | Gray/Purple | Green/Yellow |
4 (413)
4 (413)
|
672867
672867
|
|
|
|
|
|
674667
674667
|
|
|
|
|
|
3 (525)
3 (525)
|
|
|
|
|
|
|
664229
664229
|
|
|
|
|
|
2 (665)
2 (665)
|
|
|
|
|
|
|
|
|
|
|
|
|
1 (836)
1 (836)
|
|
|
|
|
|
|
456258
456258
|
|
|
|
|
|
1/0 (1044)
1/0 (1044)
|
|
|
|
|
|
|
674668
674668
|
|
|
|
|
677368 |
2/0 (1330)
2/0 (1330)
|
|
|
|
|
|
|
456257
456257
|
|
|
|
|
|
3/0 (1672)
3/0 (1672)
|
|
|
664217
664217
|
664220
664220
|
664223
664223
|
664226
664226
|
|
|
|
|
|
|
4/0 (2109)
4/0 (2109)
|
679607 |
|
456253
456253
|
456254
456254
|
456255
456255
|
|
456256
456256
|
|
|
|
|
679606
679606
|
250 (627)
250 (627)
|
649414 |
|
672218
672218
|
672217
672217
|
672219
672219
|
673792
673792
|
673791
673791
|
|
|
|
|
677370
677370
|
300 (741)
300 (741)
|
672866 |
|
674116
674116
|
674117
674117
|
674118
674118
|
674120
674120
|
674121
674121
|
|
|
|
|
|
350 (893)
350 (893)
|
649415 |
138181
138181
|
674662
674662
|
674664
674664
|
674665
674665
|
674666
674666
|
652964
652964
|
|
|
|
|
672017
672017
|
500 (1221)
500 (1221)
|
648948 |
|
646978
646978
|
646979
646979
|
646980
646980
|
646981
646981
|
677701
677701
|
456461
456461
|
456462
456462
|
456463
456463
|
456464
456464
|
646982
646982
|
600 (1480)
600 (1480)
|
649416 |
|
678431
678431
|
678432
678432
|
678434
678434
|
678435
678435
|
673748
673748
|
|
|
|
|
678436
678436
|
750 (1850)
750 (1850)
|
649549 |
|
677721
677721
|
677722
677722
|
677723
677723
|
677725
677725
|
671518
671518
|
|
|
|
|
677726
677726
|
1000 (2516)
1000 (2516)
|
674459
674459
|
|
|
|
|
|
|
|
|
|
|
|