SPEC44020 DLO TCU 2000V EPDM Insulation Thermoset CPE Jacket. RHH/RHW-2/RW90 MSHA Approved.

UL Listed as 2kV Heavy Duty Flexible Power Cable (HDFPC) DLO, Rated 90°C Dry or Wet. 2kV Type RHH/RHW-2 Flexible Power Cable Rated for Dry or Wet. CSA Listed as 2kV Type RW90. Composite Thermoset Wall EPDM Insulation Thermoset CPE Jacket. Silicone-Free. MSHA Approved

Download Category Specifications
PDF Excel Table

Application

HDFPC-DLO is a 2kV flexible power cable with a variety of possible applications such as but not limited to: Drilling rigs, railroad and transit car wiring, mining and other industrial equipment, and as flexible motor leads and wind turbine applications. The cable is suited for use in wet and dry areas, conduits, ducts, troughs, trays, and where superior electrical properties are desired. HDFPC-DLO is oil, heat, flame, abrasion, and sunlight resistant. Approved for use per the NEC® as Type RHH/RHW-2 and per the CE Code as 2kV Type RW90. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. Sizes 1/0 and Larger Rated For CT Use.

Specifications

Select a set of products below for more information:
Cond. Size (AWG/Kcmil) Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Diameter Over Insulation (in) (cm) Ground (No. x AWG) Ground Check Size Ground Check Strands Ground Insulation Thickness (mils) (mm) Inner Jacket Thickness (mils) (mm) Diameter Over Armor (in) (cm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Approx. Weight (lbs/1000') (kgs/km)
571253
12 12
0.0 0.0
19 19
0.091 0.23
45 1.14
15 0.38
0.210 0.53
36 54
560057
10 10
1.0 1.0
19 19
0.125 0.32
55 1.40
25 0.64
0.265 0.67
58 86
167014
8 8
1.0 1.0
37 37
0.145 0.37
55 1.40
30 0.76
0.330 0.84
92 137
167015
6 6
1.0 1.0
65 65
0.186 0.47
50 1.27
30 0.76
0.370 0.94
127 189
167017
4 4
1.0 1.0
105 105
0.235 0.60
60 1.52
35 0.89
0.440 1.12
196 292
167019
2 2
1.0 1.0
161 161
0.290 0.74
60 1.52
35 0.89
0.500 1.27
282 420
167021
1/0 1/0
1.0 1.0
266 266
0.379 0.96
75 1.91
55 1.40
0.645 1.64
450 670
167022
2/0 2/0
1.0 1.0
342 342
0.400 1.02
80 2.03
50 1.27
0.690 1.75
566 842
167023
3/0 3/0
1.0 1.0
418 418
0.480 1.22
80 2.03
55 1.40
0.760 1.93
676 1006
167024
4/0 4/0
1.0 1.0
532 532
0.530 1.35
80 2.03
60 1.52
0.815 2.07
815 1213
167026
262.2 262.2
1.0 1.0
646 646
0.565 1.44
80 2.03
60 1.52
0.845 2.15
974 1449
167027
313.3 313.3
1.0 1.0
779 779
0.650 1.65
90 2.29
70 1.78
0.980 2.49
1139 1695
167029
373.7 373.7
1.0 1.0
931 931
0.701 1.78
95 2.41
70 1.78
1.040 2.64
1343 1999
167030
444.4 444.4
1.0 1.0
1121 1121
0.782 1.99
90 2.29
65 1.65
1.105 2.81
1654 2461
167031
535.3 535.3
1.0 1.0
1330 1330
0.843 2.14
105 2.67
75 1.91
1.212 3.08
1889 2811
167032
646.4 646.4
1.0 1.0
1628 1628
0.890 2.26
115 2.92
80 2.03
1.290 3.28
2292 3411
167033
777.7 777.7
1.0 1.0
1924 1924
0.966 2.45
120 3.05
90 2.29
1.405 3.57
2727 4058
167035
1111 1111
1.0 1.0
2745 2745
1.168 2.97
115 2.92
95 2.41
1.640 4.17
4161 6192
Cond. Size (AWG/Kcmil) DC Resistance @ 25C (ohms/1000') (ohms/km) AC Resistance @ 75C (ohms/1000') (ohms/km) Capacitive Reactance (Mohms x 1000ft) (Mohms x km) Inductive Reactance (ohms/1000') (ohms/km) Rated Strength (lbs) (kg) Max Pull Tension (lbs) (kg) Min. Bend Radius (in) (cm) In Air Ampacity @ 60C (amps) In Air Ampacity @ 75C (amps) In Air Ampacity @ 90C (amps) In Air Ampacity @ 105C (amps) Raceway Ampacity @ 75C (amps) Raceway Ampacity @ 90C (amps)
571253
12 12
1.774 2.64
2.301 3.42
0.054 0.08
52 23.59
0.8 2.03
35 35
40 40
25 25
30 30
560057
10 10
1.081 1.61
1.302 1.94
0.05 0.07
83 37.65
1.1 2.79
50 50
55 55
35 35
40 40
167014
8 8
0.679 1.01
0.818 1.22
0.052 0.08
132 59.87
1.3 3.30
70 70
80 80
50 50
55 55
167015
6 6
0.435 0.65
0.524 0.78
0.051 0.08
209 94.80
1.5 3.81
95 95
105 105
65 65
75 75
167017
4 4
0.274 0.41
0.33 0.49
0.048 0.07
333 151.05
1.8 4.57
125 125
140 140
85 85
95 95
167019
2 2
0.172 0.26
0.207 0.31
0.045 0.07
530 240.40
2.0 5.08
170 170
190 190
115 115
130 130
167021
1/0 1/0
0.109 0.16
0.131 0.19
0.044 0.07
844 382.83
2.6 6.60
230 230
260 260
150 150
170 170
167022
2/0 2/0
0.087 0.13
0.104 0.15
0.043 0.06
1064 482.62
2.8 7.11
265 265
300 300
175 175
195 195
167023
3/0 3/0
0.069 0.10
0.083 0.12
0.042 0.06
1342 608.72
3.0 7.62
310 310
350 350
200 200
225 225
167024
4/0 4/0
0.055 0.08
0.067 0.10
0.041 0.06
1692 767.48
3.3 8.38
360 360
405 405
230 230
260 260
167026
262.2 262.2
0.026 0.04
0.033 0.05
0.031 0.05
2097 951.18
3.4 8.64
415 415
466 466
264 264
301 301
167027
313.3 313.3
0.039 0.06
0.048 0.07
0.031 0.05
2506 1136.70
3.9 9.91
460 460
518 518
298 298
332 332
167029
373.7 373.7
0.033 0.05
0.042 0.06
0.031 0.05
2989 1355.79
5.2 13.21
524 524
592 592
323 323
365 365
167030
444.4 444.4
0.026 0.04
0.04 0.06
0.029 0.04
3555 1612.52
5.5 13.97
578 578
652 652
358 358
405 405
167031
535.3 535.3
0.021 0.03
0.028 0.04
0.03 0.04
4282 1942.28
6.1 15.49
644 644
730 730
394 394
446 446
167032
646.4 646.4
0.018 0.03
0.025 0.04
0.03 0.04
5171 2345.52
6.5 16.51
720 720
812 812
439 439
496 496
167033
777.7 777.7
0.016 0.02
0.024 0.04
0.03 0.04
6221 2821.80
7.0 17.78
801 801
905 905
483 483
543 543
167035
1111 1111
0.011 0.02
0.016 0.02
0.029 0.04
8888 4031.53
8.2 20.83
993 993
1119 1119
570 570
648 648

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors (As Applicable)
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • UL 2806 Heavy Duty Flexible Power Cable (HDFPC-DLO)
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • CSA C22.2 No.230 Tray Cables - Rated TC-ER (1/0 AWG and Larger)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • MSHA Approved
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661

Construction

  1. Conductor: Flexible Stranded Rope-Lay Class I Tinned Copper per ASTM B33 and B172 (As Applicable)
  2. Binder Tape: Mylar Tape
  3. Insulation: Black Thermoset Ethylene Propylene Diene Monomer (EPDM)
  4. Jacket: Thermoset Chlorinated Polyethylene (CPE). Other colors available (see table below)