HDFPC-DLO is a 2kV flexible power cable with a variety of possible applications such as but not limited to: Drilling rigs, railroad and transit car wiring, mining and other industrial equipment, and as flexible motor leads and wind turbine applications. The cable is suited for use in wet and dry areas, conduits, ducts, troughs, trays, and where superior electrical properties are desired. HDFPC-DLO is oil, heat, flame, abrasion, and sunlight resistant. Approved for use per the NEC® as Type RHH/RHW-2 and per the CE Code as 2kV Type RW90. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. Sizes 1/0 and Larger Rated For CT Use.
Cond. Size (AWG/Kcmil) | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Insulation (in) (cm) | Ground (No. x AWG) | Ground Check Size | Ground Check Strands | Ground Insulation Thickness (mils) (mm) | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | |
571253 |
12
12
|
0.0
0.0
|
19
19
|
0.091
0.23
|
45
1.14
|
|
|
|
|
|
|
|
15
0.38
|
0.210
0.53
|
36
54
|
560057 |
10
10
|
1.0
1.0
|
19
19
|
0.125
0.32
|
55
1.40
|
|
|
|
|
|
|
|
25
0.64
|
0.265
0.67
|
58
86
|
167014 |
8
8
|
1.0
1.0
|
37
37
|
0.145
0.37
|
55
1.40
|
|
|
|
|
|
|
|
30
0.76
|
0.330
0.84
|
92
137
|
167015 |
6
6
|
1.0
1.0
|
65
65
|
0.186
0.47
|
50
1.27
|
|
|
|
|
|
|
|
30
0.76
|
0.370
0.94
|
127
189
|
167017 |
4
4
|
1.0
1.0
|
105
105
|
0.235
0.60
|
60
1.52
|
|
|
|
|
|
|
|
35
0.89
|
0.440
1.12
|
196
292
|
167019 |
2
2
|
1.0
1.0
|
161
161
|
0.290
0.74
|
60
1.52
|
|
|
|
|
|
|
|
35
0.89
|
0.500
1.27
|
282
420
|
167021 |
1/0
1/0
|
1.0
1.0
|
266
266
|
0.379
0.96
|
75
1.91
|
|
|
|
|
|
|
|
55
1.40
|
0.645
1.64
|
450
670
|
167022 |
2/0
2/0
|
1.0
1.0
|
342
342
|
0.400
1.02
|
80
2.03
|
|
|
|
|
|
|
|
50
1.27
|
0.690
1.75
|
566
842
|
167023 |
3/0
3/0
|
1.0
1.0
|
418
418
|
0.480
1.22
|
80
2.03
|
|
|
|
|
|
|
|
55
1.40
|
0.760
1.93
|
676
1006
|
167024 |
4/0
4/0
|
1.0
1.0
|
532
532
|
0.530
1.35
|
80
2.03
|
|
|
|
|
|
|
|
60
1.52
|
0.815
2.07
|
815
1213
|
167026 |
262.2
262.2
|
1.0
1.0
|
646
646
|
0.565
1.44
|
80
2.03
|
|
|
|
|
|
|
|
60
1.52
|
0.845
2.15
|
974
1449
|
167027 |
313.3
313.3
|
1.0
1.0
|
779
779
|
0.650
1.65
|
90
2.29
|
|
|
|
|
|
|
|
70
1.78
|
0.980
2.49
|
1139
1695
|
167029 |
373.7
373.7
|
1.0
1.0
|
931
931
|
0.701
1.78
|
95
2.41
|
|
|
|
|
|
|
|
70
1.78
|
1.040
2.64
|
1343
1999
|
167030 |
444.4
444.4
|
1.0
1.0
|
1121
1121
|
0.782
1.99
|
90
2.29
|
|
|
|
|
|
|
|
65
1.65
|
1.105
2.81
|
1654
2461
|
167031 |
535.3
535.3
|
1.0
1.0
|
1330
1330
|
0.843
2.14
|
105
2.67
|
|
|
|
|
|
|
|
75
1.91
|
1.212
3.08
|
1889
2811
|
167032 |
646.4
646.4
|
1.0
1.0
|
1628
1628
|
0.890
2.26
|
115
2.92
|
|
|
|
|
|
|
|
80
2.03
|
1.290
3.28
|
2292
3411
|
167033 |
777.7
777.7
|
1.0
1.0
|
1924
1924
|
0.966
2.45
|
120
3.05
|
|
|
|
|
|
|
|
90
2.29
|
1.405
3.57
|
2727
4058
|
167035 |
1111
1111
|
1.0
1.0
|
2745
2745
|
1.168
2.97
|
115
2.92
|
|
|
|
|
|
|
|
95
2.41
|
1.640
4.17
|
4161
6192
|
Cond. Size (AWG/Kcmil) | DC Resistance @ 25C (ohms/1000') (ohms/km) | AC Resistance @ 75C (ohms/1000') (ohms/km) | Capacitive Reactance (Mohms x 1000ft) (Mohms x km) | Inductive Reactance (ohms/1000') (ohms/km) | Rated Strength (lbs) (kg) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | In Air Ampacity @ 60C (amps) | In Air Ampacity @ 75C (amps) | In Air Ampacity @ 90C (amps) | In Air Ampacity @ 105C (amps) | Raceway Ampacity @ 75C (amps) | Raceway Ampacity @ 90C (amps) | |
571253 |
12
12
|
1.774
2.64
|
2.301
3.42
|
|
0.054
0.08
|
|
52
23.59
|
0.8
2.03
|
|
35
35
|
40
40
|
|
25
25
|
30
30
|
560057 |
10
10
|
1.081
1.61
|
1.302
1.94
|
|
0.05
0.07
|
|
83
37.65
|
1.1
2.79
|
|
50
50
|
55
55
|
|
35
35
|
40
40
|
167014 |
8
8
|
0.679
1.01
|
0.818
1.22
|
|
0.052
0.08
|
|
132
59.87
|
1.3
3.30
|
|
70
70
|
80
80
|
|
50
50
|
55
55
|
167015 |
6
6
|
0.435
0.65
|
0.524
0.78
|
|
0.051
0.08
|
|
209
94.80
|
1.5
3.81
|
|
95
95
|
105
105
|
|
65
65
|
75
75
|
167017 |
4
4
|
0.274
0.41
|
0.33
0.49
|
|
0.048
0.07
|
|
333
151.05
|
1.8
4.57
|
|
125
125
|
140
140
|
|
85
85
|
95
95
|
167019 |
2
2
|
0.172
0.26
|
0.207
0.31
|
|
0.045
0.07
|
|
530
240.40
|
2.0
5.08
|
|
170
170
|
190
190
|
|
115
115
|
130
130
|
167021 |
1/0
1/0
|
0.109
0.16
|
0.131
0.19
|
|
0.044
0.07
|
|
844
382.83
|
2.6
6.60
|
|
230
230
|
260
260
|
|
150
150
|
170
170
|
167022 |
2/0
2/0
|
0.087
0.13
|
0.104
0.15
|
|
0.043
0.06
|
|
1064
482.62
|
2.8
7.11
|
|
265
265
|
300
300
|
|
175
175
|
195
195
|
167023 |
3/0
3/0
|
0.069
0.10
|
0.083
0.12
|
|
0.042
0.06
|
|
1342
608.72
|
3.0
7.62
|
|
310
310
|
350
350
|
|
200
200
|
225
225
|
167024 |
4/0
4/0
|
0.055
0.08
|
0.067
0.10
|
|
0.041
0.06
|
|
1692
767.48
|
3.3
8.38
|
|
360
360
|
405
405
|
|
230
230
|
260
260
|
167026 |
262.2
262.2
|
0.026
0.04
|
0.033
0.05
|
|
0.031
0.05
|
|
2097
951.18
|
3.4
8.64
|
|
415
415
|
466
466
|
|
264
264
|
301
301
|
167027 |
313.3
313.3
|
0.039
0.06
|
0.048
0.07
|
|
0.031
0.05
|
|
2506
1136.70
|
3.9
9.91
|
|
460
460
|
518
518
|
|
298
298
|
332
332
|
167029 |
373.7
373.7
|
0.033
0.05
|
0.042
0.06
|
|
0.031
0.05
|
|
2989
1355.79
|
5.2
13.21
|
|
524
524
|
592
592
|
|
323
323
|
365
365
|
167030 |
444.4
444.4
|
0.026
0.04
|
0.04
0.06
|
|
0.029
0.04
|
|
3555
1612.52
|
5.5
13.97
|
|
578
578
|
652
652
|
|
358
358
|
405
405
|
167031 |
535.3
535.3
|
0.021
0.03
|
0.028
0.04
|
|
0.03
0.04
|
|
4282
1942.28
|
6.1
15.49
|
|
644
644
|
730
730
|
|
394
394
|
446
446
|
167032 |
646.4
646.4
|
0.018
0.03
|
0.025
0.04
|
|
0.03
0.04
|
|
5171
2345.52
|
6.5
16.51
|
|
720
720
|
812
812
|
|
439
439
|
496
496
|
167033 |
777.7
777.7
|
0.016
0.02
|
0.024
0.04
|
|
0.03
0.04
|
|
6221
2821.80
|
7.0
17.78
|
|
801
801
|
905
905
|
|
483
483
|
543
543
|
167035 |
1111
1111
|
0.011
0.02
|
0.016
0.02
|
|
0.029
0.04
|
|
8888
4031.53
|
8.2
20.83
|
|
993
993
|
1119
1119
|
|
570
570
|
648
648
|