Fire Alarm FPLP

60°C 300V PLENUM RATED

Download Category Specifications:
PDF Excel Table

Application

FIRE PROTECTIVE SIGNALING POWER LIMITED CIRCUIT CABLE

Specifications

measurement
imperial metric
Select a set of products below for more information:
Conductor Ground Wire
No. of Conductors Size (AWG or kcmil) No. of Strands Insulation Thickness (mils) (mm) Size (AWG) No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity
G40005 2 2 18 AWG 18 AWG 1 1 144 3.66 16 23
G40505 4 4 18 AWG 18 AWG 1 1 168 4.27 28 42
G40503 6 6 18 AWG 18 AWG 1 1 184 4.67 41 60
G50013 2 2 16 AWG 16 AWG 1 1 176 4.47 24 36
G50054 4 4 16 AWG 16 AWG 1 1 197 5.00 44 65
G60004 2 2 14 AWG 14 AWG 1 1 196 4.98 34 51
G60346 4 4 14 AWG 14 AWG 1 1 234 5.94 65 96
G70009 2 2 12 AWG 12 AWG 1 1 226 5.74 49 74

Standards & References

UL 1424 FPLR, NEC article 760

  • UL 13 CL3R, NEC article 725
  • UL 444 CMR, NEC article 800
  • UL 1666 Vertical Riser / CSA FT4 (UL 1581)
  • CSA C22.2 CMG
  • RoHS (European Directive 22/95/EC)

Construction

Conductors: 22 AWG SOLID BARE COPPER

  • CONDUCTOR: Solid Bare Copper or Stranded Bare Copper
  • INSULATION: LS-PVC
  • COLOR CODE: Black, Red, Green, Yellow.
  • ASSEMBLY: Cabled with ripcord, and jacketed
  • JACKET: LS-PVC
  • Both insulation and jacket materials are silicone free

Resources

There are no downloadable resources for this product.