Southwire’s 15KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where su- perior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. ST1 (low smoke) Rated for sizes 1/0 and larger. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure. 2x5 mils tape shield for higher short circuit withstand.
Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Inner Layer Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Outer Layer Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Conduit Size (in) (cm) | |
More Options |
250 KCMIL
250 KCMIL
|
22
22
|
0.520
1.32
|
1.006
2.56
|
220
5.59
|
1.066
2.71
|
80
2.03
|
1.266
3.22
|
930
1384
|
1500
680.39
|
15.1
38.35
|
3.5
8.89
|
More Options |
500 KCMIL
500 KCMIL
|
34
34
|
0.735
1.87
|
1.244
3.16
|
220
5.59
|
1.304
3.31
|
80
2.03
|
1.504
3.82
|
1341
1996
|
3000
1360.78
|
18.0
45.72
|
4.5
11.43
|
More Options |
750 KCMIL
750 KCMIL
|
58
58
|
0.908
2.31
|
1.426
3.62
|
220
5.59
|
1.486
3.77
|
80
2.03
|
1.746
4.43
|
1821
2710
|
4500
2041.16
|
20.9
53.09
|
5.0
12.70
|
* Strand count meets minimum number per ASTM
Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles | Allowable Ampacity In Duct 90C | Allowable Ampacity In Duct 105C | Allowable Ampacity In Air 90C | Allowable Ampacity In Air 105C | |
More Options |
250 KCMIL
250 KCMIL
|
0.071
0.11
|
0.090
0.13
|
0.034
0.05
|
0.042
0.06
|
0.447 + j0.321
0.447 + j0.321
|
0.091 + j0.04
0.091 + j0.04
|
3333
3333
|
250
250
|
270
270
|
345
345
|
385
385
|
More Options |
500 KCMIL
500 KCMIL
|
0.035
0.05
|
0.046
0.07
|
0.026
0.04
|
0.037
0.06
|
0.384 + j0.26
0.384 + j0.26
|
0.047 + j0.036
0.047 + j0.036
|
3999
3999
|
370
370
|
400
400
|
535
535
|
600
600
|
More Options |
750 KCMIL
750 KCMIL
|
0.024
0.04
|
0.033
0.05
|
0.022
0.03
|
0.035
0.05
|
0.353 + j0.22
0.353 + j0.22
|
0.034 + j0.034
0.034 + j0.034
|
4566
4566
|
455
455
|
490
490
|
700
700
|
780
780
|
* NEC ampacities are based on:
* For Duct: Table 310.60(C)(12) Detail 1.
* For Free Air: Table 310.60(C)(4).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.
* Capacitive Reactance is between Phase-to-Shield.