Southwire’s 5KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.
Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Inner Layer Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Outer Layer Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Conduit Size (in) (cm) | |
More Options |
2 AWG
2 AWG
|
7
7
|
0.268
0.68
|
0.536
1.36
|
115
2.92
|
0.640
1.63
|
55
1.40
|
0.790
2.01
|
342
509
|
398
180.53
|
9.4
23.88
|
2.5
6.35
|
More Options |
1/0 AWG
1/0 AWG
|
10
10
|
0.336
0.85
|
0.604
1.53
|
115
2.92
|
0.664
1.69
|
55
1.40
|
0.814
2.07
|
377
561
|
633
287.12
|
9.7
24.64
|
2.5
6.35
|
More Options |
2/0 AWG
2/0 AWG
|
12
12
|
0.376
0.96
|
0.644
1.64
|
115
2.92
|
0.704
1.79
|
80
2.03
|
0.884
2.25
|
446
664
|
798
361.97
|
10.6
26.92
|
2.5
6.35
|
More Options |
4/0 AWG
4/0 AWG
|
19
19
|
0.474
1.20
|
0.743
1.89
|
115
2.92
|
0.803
2.04
|
80
2.03
|
0.983
2.50
|
569
847
|
1269
575.61
|
11.7
29.72
|
3.0
7.62
|
More Options |
350 KCMIL
350 KCMIL
|
35
35
|
0.615
1.56
|
0.892
2.27
|
115
2.92
|
0.952
2.42
|
80
2.03
|
1.132
2.88
|
777
1156
|
2100
952.54
|
13.5
34.29
|
3.5
8.89
|
More Options |
500 KCMIL
500 KCMIL
|
35
35
|
0.735
1.87
|
1.034
2.63
|
115
2.92
|
1.094
2.78
|
80
2.03
|
1.274
3.24
|
990
1473
|
3000
1360.78
|
15.2
38.61
|
3.5
8.89
|
More Options |
750 KCMIL
750 KCMIL
|
58
58
|
0.908
2.31
|
1.206
3.06
|
115
2.92
|
1.266
3.22
|
80
2.03
|
1.446
3.67
|
1315
1957
|
4500
2041.16
|
17.3
43.94
|
4.0
10.16
|
More Options |
1000 KCMIL
1000 KCMIL
|
58
58
|
1.060
2.69
|
1.044
2.65
|
115
2.92
|
1.104
2.80
|
80
2.03
|
1.598
4.06
|
1627
2421
|
6000
2721.55
|
19.1
48.51
|
4.5
11.43
|
* Strand count meets minimum number per ASTM
Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles | Allowable Ampacity In Duct 90C | Allowable Ampacity In Duct 105C | Allowable Ampacity In Air 90C | Allowable Ampacity In Air 105C | |
More Options |
2 AWG
2 AWG
|
0.267
0.40
|
0.336
0.50
|
0.036
0.05
|
0.045
0.07
|
0.7 + j0.521
0.7 + j0.521
|
0.336 + j0.044
0.336 + j0.044
|
1877
1877
|
115
115
|
125
125
|
150
150
|
165
165
|
More Options |
1/0 AWG
1/0 AWG
|
0.168
0.25
|
0.211
0.31
|
0.030
0.04
|
0.041
0.06
|
0.581 + j0.482
0.581 + j0.482
|
0.211 + j0.04
0.211 + j0.04
|
2088
2088
|
150
150
|
160
160
|
200
200
|
225
225
|
More Options |
2/0 AWG
2/0 AWG
|
0.133
0.20
|
0.167
0.25
|
0.028
0.04
|
0.041
0.06
|
0.537 + j0.46
0.537 + j0.46
|
0.167 + j0.04
0.167 + j0.04
|
2212
2212
|
170
170
|
185
185
|
230
230
|
260
260
|
More Options |
4/0 AWG
4/0 AWG
|
0.084
0.13
|
0.105
0.16
|
0.023
0.03
|
0.038
0.06
|
0.476 + j0.413
0.476 + j0.413
|
0.105 + j0.037
0.105 + j0.037
|
2515
2515
|
225
225
|
245
245
|
310
310
|
350
350
|
More Options |
350 KCMIL
350 KCMIL
|
0.050
0.07
|
0.065
0.10
|
0.019
0.03
|
0.036
0.05
|
0.43 + j0.352
0.43 + j0.352
|
0.066 + j0.034
0.066 + j0.034
|
2977
2977
|
305
305
|
325
325
|
430
430
|
480
480
|
More Options |
500 KCMIL
500 KCMIL
|
0.035
0.05
|
0.046
0.07
|
0.016
0.02
|
0.034
0.05
|
0.403 + j0.312
0.403 + j0.312
|
0.047 + j0.032
0.047 + j0.032
|
3349
3349
|
370
370
|
400
400
|
545
545
|
605
605
|
More Options |
750 KCMIL
750 KCMIL
|
0.024
0.04
|
0.033
0.05
|
0.014
0.02
|
0.032
0.05
|
0.374 + j0.261
0.374 + j0.261
|
0.034 + j0.031
0.034 + j0.031
|
3916
3916
|
470
470
|
505
505
|
710
710
|
790
790
|
More Options |
1000 KCMIL
1000 KCMIL
|
0.018
0.03
|
0.026
0.04
|
0.012
0.02
|
0.031
0.05
|
0.352 + j0.227
0.352 + j0.227
|
0.027 + j0.03
0.027 + j0.03
|
4387
4387
|
545
545
|
590
590
|
855
855
|
950
950
|
* NEC ampacities are based on:
* For Duct: Table 310.60(C)(12) Detail 1.
* For Free Air: Table 310.60(C)(4).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.
* Capacitive Reactance is between Phase-to-Shield.