Southwire’s 2.4KV XLPE cables are suited for use in dry areas, conduits, ducts, troughs, trays and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation, 130°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. Rated for 1000 lbs./FT maximum sidewall pressure. Silicone Free.
Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Inner Layer Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Conduit Size (in) (cm) | |
More Options |
6 AWG
6 AWG
|
7
7
|
0.174
0.44
|
110
2.79
|
0.430
1.09
|
137
204
|
210
95.25
|
3.4
8.64
|
1.5
3.81
|
More Options |
4 AWG
4 AWG
|
7
7
|
0.225
0.57
|
110
2.79
|
0.481
1.22
|
215
320
|
334
151.50
|
3.8
9.65
|
1.5
3.81
|
More Options |
2 AWG
2 AWG
|
7
7
|
0.283
0.72
|
110
2.79
|
0.537
1.36
|
313
466
|
531
240.86
|
4.3
10.92
|
1.5
3.81
|
Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity In Duct 90C | Allowable Ampacity In Air 90C | |
More Options |
6 AWG
6 AWG
|
0.411
0.61
|
0.515
0.77
|
0.042
0.06
|
85
85
|
110
110
|
More Options |
4 AWG
4 AWG
|
0.258
0.38
|
0.323
0.48
|
0.039
0.06
|
110
110
|
145
145
|
More Options |
2 AWG
2 AWG
|
0.162
0.24
|
0.203
0.30
|
0.036
0.05
|
145
145
|
190
190
|
* NEC ampacities are based on:
* For Duct: Table 310.60(C)(11) Detail 1.
* For Free Air: Table 310.60(C)(3).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.