Southwire’s 2.4KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -40°C for cold bend and cold impact and marked with "LTGG" when CSA listed or dual UL/CSA listed. For uses in Class I and II, Division 2 hazardous locations per NEC Article 501 and 502.Rated for 1000 lbs./FT maximum sidewall pressure.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
600429 |
3
3
|
2 AWG
2 AWG
|
7
7
|
90
2.29
|
6
6
|
|
1239
31.48
|
1143
1702
|
|
600411 |
3
3
|
1/0 AWG
1/0 AWG
|
19
19
|
90
2.29
|
4
4
|
|
1422
36.14
|
1689
2513
|
|
600387 |
3
3
|
500 KCMIL
500 KCMIL
|
37
37
|
90
2.29
|
1
1
|
|
2437
61.91
|
6310
9391
|
|