Aluminum Conductor. EPR Insulation. Bare Copper Concentric Neutrals. Low Density Polyethylene Jacket.
Predominantly used for primary underground distribution in conduit systems suitable for use in wet or dry locations, direct burial, underground duct, and where exposed to sunlight. To be used at 15,000 volts or less and at conductor temperatures not to exceed 105°C for normal operation.
Conductor | ||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | |
More Options |
1
1
|
2 AWG
2 AWG
|
1
1
|
220
5.59
|
1046
26.57
|
561
834
|
More Options |
1
1
|
1/0 AWG
1/0 AWG
|
19
19
|
220
5.59
|
1140
28.96
|
734
1092
|
More Options |
1
1
|
2/0 AWG
2/0 AWG
|
19
19
|
220
5.59
|
1183
30.05
|
835
1243
|
More Options |
1
1
|
4/0 AWG
4/0 AWG
|
19
19
|
220
5.59
|
1286
32.67
|
868
1291
|
More Options |
1
1
|
250 KCMIL
250 KCMIL
|
37
37
|
220
5.59
|
1376
34.96
|
929
1382
|
More Options |
1
1
|
350 KCMIL
350 KCMIL
|
37
37
|
175
4.45
|
1389
35.29
|
1124
1673
|
More Options |
1
1
|
500 KCMIL
500 KCMIL
|
37
37
|
220
5.59
|
1640
41.67
|
1581
2352
|
More Options |
1
1
|
750 KCMIL
750 KCMIL
|
61
61
|
220
5.59
|
1883
47.84
|
2181
3246
|
More Options |
1
1
|
1000 KCMIL
1000 KCMIL
|
61
61
|
220
5.59
|
2104
53.46
|
2789
4151
|
More Options |
1
1
|
1100 KCMIL
1100 KCMIL
|
58
58
|
220
5.59
|
2073
52.67
|
2546
3789
|
Southwire 15kV Primary UD EPR Cable meets or exceeds the following ASTM specifications:
The cable is composed of a moisture blocked reverse lay compressed stranded 1350-H16/26 aluminum phase conductor, covered by a semi-conducting cross-linked polyethylene strand shield, an ethylene propylene rubber primary insulation, and a semiconducting cross-linked polyethylene insulation shield. Conductors are available with 133% insulation level. A concentric neutral of bare copper wires and a sunlight resistant, -40°C rated, insulating linear low density polyethylene jacket are applied over the insulation shield. The cable is identified by surface print on the jacket and with the lightning bolt symbol for supply cables indented in the jacket. Has red extruded stripes.