Predominantly used for primary underground distribution in conduit systems suitable for use in wet or dry locations, direct burial, underground duct, and where exposed to sunlight. To be used at 15,000 volts or less and at conductor temperatures not to exceed 90°C for normal operation.
Conductor | ||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | |
More Options |
1
1
|
2 AWG
2 AWG
|
7
7
|
175
4.45
|
981
24.92
|
476
709
|
More Options |
1
1
|
1 AWG
1 AWG
|
1
1
|
220
5.59
|
1098
27.89
|
600
892
|
More Options |
3
3
|
1/0 AWG
1/0 AWG
|
19
19
|
175
4.45
|
|
1498
2230
|
More Options |
1
1
|
1/0 AWG
1/0 AWG
|
19
19
|
175
4.45
|
1050
26.68
|
619
921
|
More Options |
1
1
|
2/0 AWG
2/0 AWG
|
19
19
|
220
5.59
|
1183
30.05
|
780
1161
|
More Options |
1
1
|
3/0 AWG
3/0 AWG
|
19
19
|
220
5.59
|
1231
31.27
|
899
1338
|
More Options |
1
1
|
4/0 AWG
4/0 AWG
|
19
19
|
175
4.45
|
1229
31.23
|
1006
1497
|
More Options |
1
1
|
350 KCMIL
350 KCMIL
|
37
37
|
175
4.45
|
1389
35.29
|
1065
1584
|
More Options |
1
1
|
500 KCMIL
500 KCMIL
|
37
37
|
220
5.59
|
1640
41.67
|
1491
2219
|
More Options |
1
1
|
750 KCMIL
750 KCMIL
|
61
61
|
220
5.59
|
1925
48.92
|
2075
3088
|
More Options |
1
1
|
1000 KCMIL
1000 KCMIL
|
61
61
|
220
5.59
|
2062
52.39
|
2314
3444
|
Southwire 15kV HI-DRI Primary UD TRXLP Cable meets or exceeds the following ASTM specifications:
The cable is composed of a moisture blocked unilay compressed stranded 1350-H16/26 aluminum phase conductor, covered by a semi-conducting cross-linked polyethylene strand shield, a tree-retardant cross-linked polyethylene primary insulation, and a semi-conducting cross-linked polyethylene insulation shield. Conductors are available with 100% insulation level. Has a Super Smooth conductor shield. A concentric neutral of bare copper wires and a sunlight resistant, -40°C rated, insulating linear low density polyethylene jacket are applied over the insulation shield. The cable is identified by surface print on the jacket and with the lightning bolt symbol for supply cables indented in the jacket. Has red extruded stripes.