Alumaflex™ Type MC AL Feeder XHHW-2 Conductors

2/3 AWG AlumaFlex™ XHHW-2 Insulated Singles with 8000 series Triple E™ Aluminum Alloy. Bare AlumaFlex™ Aluminum Alloy Grounding Conductor. UL Listed. 600 Volts. Lightweight Aluminum Interlocked Armor

Download Category Specifications
PDF Excel Table

Application & Features

Suitable for use as follows:

  • Branch, feeder and service power distribution under high ambient temperatures in commercial, industrial, institutional, and multi-residential buildings.
  • Power, lighting, control, and signal circuits.
  • Fished or embedded in plaster.
  • Concealed or exposed installations.
  • Environmental air-handling spaces per NEC 300.22 (C).
  • Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
  • Installation in cable tray and approved raceways
  • Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2).
  • Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.

Specifications

Select a set of products below for more information:
Conductor Ground Wire
No. of Conductors Size (AWG or kcmil) (mm2) No. of Strands Insulation Thickness (mils) (mm) Size (AWG) Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km)
More Options
3 3
6 AWG 6 AWG
7 7
45 1.14
6 6
839 21.33
242 360
More Options
4 4
6 AWG 6 AWG
7 7
45 1.14
6 6
925 23.50
296 440
More Options
3 3
4 AWG 4 AWG
7 7
45 1.14
6 6
956 24.28
315 469
More Options
4 4
4 AWG 4 AWG
7 7
45 1.14
6 6
1036 26.32
382 569
More Options
3 3
2 AWG 2 AWG
6 6
45 1.14
4 4
1082 27.49
417 621
More Options
4 4
2 AWG 2 AWG
6 6
45 1.14
4 4
1184 30.09
530 789
More Options
3 3
1 AWG 1 AWG
8 8
55 1.40
4 4
1101 27.98
491 731
More Options
4 4
1 AWG 1 AWG
8 8
55 1.40
4 4
1322 33.59
647 963
More Options
3 3
1/0 AWG 1/0 AWG
10 10
55 1.40
4 4
1154 29.31
569 847
More Options
4 4
1/0 AWG 1/0 AWG
10 10
55 1.40
4 4
1296 32.93
740 1102
More Options
3 3
2/0 AWG 2/0 AWG
12 12
55 1.40
4 4
1405 35.70
711 1058
More Options
4 4
2/0 AWG 2/0 AWG
12 12
55 1.40
4 4
1382 35.12
875 1302
More Options
3 3
3/0 AWG 3/0 AWG
15 15
55 1.40
4 4
1311 33.31
786 1170
More Options
4 4
3/0 AWG 3/0 AWG
15 15
55 1.40
4 4
1584 40.24
1113 1656
More Options
3 3
4/0 AWG 4/0 AWG
19 19
55 1.40
2 2
1538 39.09
1037 1543
More Options
4 4
4/0 AWG 4/0 AWG
19 19
55 1.40
2 2
1726 43.85
1357 2019
More Options
3 3
250 KCMIL 250 KCMIL
22 22
65 1.65
2 2
1656 42.08
1204 1792
More Options
4 4
250 KCMIL 250 KCMIL
22 22
65 1.65
1 1
1883 47.84
1601 2382
More Options
4 4
300 KCMIL 300 KCMIL
35 35
65 1.65
1 1
1991 50.58
1841 2740
More Options
3 3
350 KCMIL 350 KCMIL
35 35
65 1.65
2 2
1830 46.49
1549 2306
More Options
4 4
350 KCMIL 350 KCMIL
35 35
65 1.65
1/0 1/0
2110 53.61
2092 3113
More Options
4 4
400 KCMIL 400 KCMIL
35 35
65 1.65
1/0 1/0
2203 55.97
2333 3472
More Options
4 4
500 KCMIL 500 KCMIL
35 35
65 1.65
2/0 2/0
2391 60.75
2805 4174
More Options
4 4
750 KCMIL 750 KCMIL
58 58
80 2.03
3/0 3/0
2853 72.47
4096 6096
More Options
4 4
1000 KCMIL 1000 KCMIL
61 61
80 2.03
600 600
3418 86.82
5635 8386

Standards & References

Southwire AlumaFlex™ Type MC-XHHW-2 Cable meets or exceeds the requirements:

  • UL 44
  • UL 1569
  • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
  • ICEA S-95-658 (NEMA WC70)
  • Federal Specification A-A59544 (formerly J-C-30B)
  • IEEE 1202 (70,000 Btu/hr) Vertical Cable Tray Flame Test
  • NFPA 70 (National Electrical Code), Article 330
  • Listed for use in UL 1, 2, and 3 Hour Through-Penetration Firestop Systems
  • REACH/RoHS-2 (Chemical Limit) Compliant

Construction

Southwire AlumaFlex™Type MC-XHHW-2 Cable with Triple E™Aluminum Alloy is constructed with Type XHHW-2 conductors rated 90˚ C dry, and a bare equipment grounding conductor. Conductors are AlumaFlex™ AA-8000 series aluminum alloy compact stranded. A binder tape is wrapped over the conductors. Aluminum interlocking armor is applied over the assembly. Refer to color chart for conductor color sequence.